7<br />

98(110) Control keypad<br />

READY<br />

READY<br />

I/Oterm<br />

I/Oterm<br />

I/Oterm<br />

P6.7.2 P6.7.2 P6.7.2<br />

Fan control<br />

Continuous<br />

Figure 7-22. Fan control function<br />

Fan control<br />

Continuous<br />

enter<br />

Fan control<br />

READY<br />

Temperature<br />

HMI acknowledge timeout (P6.7.3)<br />

This function allows the user to change the timeout of the HMI acknowledgement time.<br />

Note! If the frequency drive has been connected to the PC with a normal cable, the default<br />

values of parametres 6.7.3 and 6.7.4 (200 and 5) must not be changed.<br />

If the frequency drive has been connected to the PC via a modem and there is a delay in<br />

transferring messages, the value of par. 6.7.3 must be set according to the delay as follows:<br />

Example:<br />

• Transfer delay between the frequency drive and the PC = 600 ms<br />

• The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving<br />

delay)<br />

• The corresponding setting shall be entered to the [Misc]-part of the<br />

NCDrive.ini file:<br />

Retries = 5<br />

AckTimeOut = 1200<br />

TimeOut = 6000<br />

It must also be considered that intervals that are shorter than the AckTimeOut-time cannot be<br />

used in NCDrive monitoring.<br />

Enter the edit mode by pushing the right arrow menu button. Use the Browser buttons to change<br />

the acknowledgement time. Accept the change with the Enter button or return to the previous level<br />

with the left arrow menu button .<br />

P6.7.3<br />

READY<br />

I/Oterm<br />

HMI ACK timeout<br />

200ms<br />

P6.7.3<br />

READY<br />

I/Oterm<br />

HMI ACK timeout<br />

200ms<br />

enter<br />

Figure 7-23. HMI acknowledge timeout<br />

Number of retries to receive HMI acknowledgement (P6.7.4)<br />

With this parameter it is possible to set the number of times the drive will try to receive<br />

acknowledgement if this does not happen within the acknowledgement time (P6.7.3) or if the<br />

received acknowledgement is faulty.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!