88 Multi-purpose Control Application Honeywell<br />

6.6.9.1 NXP drives: Closed Loop parameters (Control keypad: Menu M2 G2.6.27)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.6.27.1<br />

Magnetizing<br />

current<br />

0,00 100,00 A 0,00 612 If zero internally calculated<br />

P2.6.27.2<br />

Speed control P<br />

gain<br />

1 1000 30 613<br />

P2.6.27.3<br />

Speed control I<br />

Negative value uses 1 ms<br />

-32000 3200,0 ms 100,0 614<br />

time<br />

accuracy instead of 0,1 ms<br />

P2.6.27.5<br />

Acceleration<br />

compensation<br />

0,00 300,00 s 0,00 626<br />

P2.6.27.6 Slip adjust 0 500 % 75 619<br />

P2.6.27.7<br />

Magnetizing<br />

current at start<br />

0 I L A 0,00 627<br />

P2.6.27.8<br />

Magnetizing time<br />

at start<br />

0 32000 ms 0 628<br />

P2.6.27.9<br />

0-speed time at<br />

start<br />

0 32000 ms 100 615<br />

P2.6.27.10<br />

0-speed time at<br />

stop<br />

0 32000 ms 100 616<br />

P2.6.27.11 Start-up torque 0 3 0 621<br />

0=Not used<br />

1=Torque memory<br />

2=Torque reference<br />

3=Start-up torque fwd/rev<br />

P2.6.27.12<br />

Start-up torque<br />

FWD<br />

–300,0 300,0 % 0,0 <strong>63</strong>3<br />

P2.6.27.13<br />

Start-up torque<br />

REV<br />

–300,0 300,0 % 0,0 <strong>63</strong>4<br />

P2.6.27.15 Encoder filter time 0,0 100,0 ms 0,0 618<br />

P2.6.27.17<br />

Current control<br />

P gain<br />

0,00 100,00 % 40,00 617<br />

P2.6.27.19<br />

Generator power<br />

limit<br />

0,0 300,0 % 300,0 1290<br />

P2.6.27.20<br />

Motoring power<br />

limit<br />

0,0 300,0 % 300,0 1289<br />

P2.6.27.21<br />

Negative torque<br />

limit<br />

0,0 300,0 % 300,0 645<br />

P2.6.27.22<br />

Positive torque<br />

limit<br />

0,0 300,0 % 300,0 646<br />

P2.6.27.23 Flux off delay -1 32000 s 0 1402 -1=Always<br />

P2.6.27.24 Stop state flux 0,0 150,0 % 100,0 1401<br />

P2.6.27.25 SPC f1 point 0,00 320,00 Hz 0,00 1301<br />

P2.6.27.26 SPC f0 point 0,00 320,00 Hz 0,00 1300<br />

P2.6.27.27 SPC Kp f0 0 1000 % 100 1299<br />

P2.6.27.28 SPC Kp FWP 0 1000 % 100 1298<br />

P2.6.27.29<br />

SPC torque<br />

minimum<br />

0 400,0 % 0,0 1296<br />

P2.6.27.30<br />

SPC torque<br />

minimum Kp<br />

0 1000 % 100 1295<br />

P2.6.27.31 SPC Kp TC torque 0 1000 ms 0 1297<br />

P2.6.27.32 Flux reference 0,0 500,0 % 100,0 1250<br />

P2.6.27.33<br />

Speed error filter<br />

TC<br />

0 1000 ms 0 1311<br />

Table 6-26. Closed Loop motor control parameters (G2.6.4)<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!