66 Multi-purpose Control Application Honeywell<br />

6.4.2 Defining a terminal for a certain function with NCDrive programming tool<br />

If you use the NCDrive Programming Tool for parametrizing you will have to establish the connection<br />

between the function and input/output in the same way as with the control panel. Just pick<br />

the address code from the drop-down menu in the Value column (see the Figure below).<br />

Figure 6-2. Screenshot of NCDrive programming tool; Entering the address code<br />

!<br />

WARNING<br />

Be ABSOLUTELY sure not to connect two functions to one and<br />

same output in order to avoid function overruns and to ensure<br />

flawless operation.<br />

Note: The inputs, unlike the outputs, cannot be changed in RUN state.<br />

6.4.3 Defining unused inputs/outputs<br />

All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the terminal<br />

number. The value 0.1 is also the default value for most of the functions. However, if you want<br />

to use the values of a digital input signal for e.g. testing purposes only, you can set the board slot<br />

value to 0 and the terminal number to any number between 2…10 to place the input to a TRUE<br />

state. In other words, the value 1 corresponds to 'open contact' and values 2 to 10 to 'closed<br />

contact'.<br />

In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0% signal<br />

level, value 2 corresponds to 20%, value 3 to 30% and so on. Giving value 10 for the terminal<br />

number corresponds to 100% signal level.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!