Honeywell Description of Parameters 123<br />

108 U/f ration selection 234567 (2.6.3)<br />

Linear:<br />

0<br />

Squared:<br />

1<br />

The voltage of the motor changes linearly with the frequency in the constant<br />

flux area from 0 Hz to the field weakening point where the nominal voltage is<br />

supplied to the motor. Linear U/f ration should be used in constant torque<br />

applications. This default setting should be used if there is no special<br />

need for another setting.<br />

The voltage of the motor changes following a squared curve form with the<br />

frequency in the area from 0 Hz to the field weakening point where the nominal<br />

voltage is also supplied to the motor. The motor runs undermagnetised<br />

below the field weakening point and produces less torque and electromechanical<br />

noise. Squared U/f ratio can be used in applications where<br />

torque demand of the load is proportional to the square of the speed, e.g. in<br />

centrifugal fans and pumps.<br />

Un<br />

ID603<br />

U[V]<br />

Default: Nominal<br />

voltage of the motor<br />

Field weakening<br />

point<br />

Linear<br />

Squared<br />

Default: Nominal<br />

frequency of the<br />

motor<br />

f[Hz]<br />

NX12K07<br />

Figure 8-1. Linear and squared change of motor voltage<br />

Programmable U/f curve:<br />

2 The U/f curve can be programmed with three different points. Programmable<br />

U/f curve can be used if the other settings do not satisfy the needs of the<br />

application.<br />

Un<br />

ID603<br />

U[V]<br />

Default: Nominal<br />

voltage of the motor<br />

Field weakening point<br />

ID605<br />

(Def. 10%)<br />

ID606<br />

(Def. 1.3%)<br />

ID604<br />

(Def. 5 Hz)<br />

Figure 8-2. Programmable U/f curve<br />

ID602<br />

Default: Nominal<br />

frequency of the motor<br />

f[Hz]<br />

NX12K08<br />

Linear with flux optimisation:<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!