182 Description of Parameters Honeywell<br />

708 Motor thermal protection: Motor duty cycle 234567 (2.7.12)<br />

Defines how much of the nominal motor load is applied.<br />

The value can be set to 0%…100%. See chapter 9.4.<br />

Motor temperature<br />

105%<br />

Trip area<br />

Motor<br />

current<br />

I/I T<br />

Fault/warning<br />

par. ID704<br />

Motor temperature<br />

Time constant T *)<br />

Θ = (I/I T ) 2 x (1-e -t/T )<br />

*) Changes by motor size and<br />

adjusted with parameter ID707<br />

Time<br />

NX12k82<br />

Figure 8-48. Motor temperature calculation<br />

709 Stall protection 234567 (2.7.13)<br />

0 = No response<br />

1 = Warning<br />

2 = Fault, stop mode after fault according to ID506<br />

3 = Fault, stop mode after fault always by coasting<br />

Setting the parameter to 0 will deactivate the protection and reset the stall time counter.<br />

See chapter 9.5.<br />

710 Stall current limit 234567 (2.7.14)<br />

The current can be set to 0.0…2*I H . For a<br />

stall stage to occur, the current must have<br />

exceeded this limit. See Figure 8-49. The<br />

software does not allow entering a greater<br />

value than 2*I H . If parameter ID107 Nominal<br />

current limit of motor is changed, this<br />

parameter is automatically calculated to 90%<br />

of the current limit. See chapter 9.5.<br />

Par. ID710<br />

I<br />

Stall area<br />

f<br />

Par. ID712<br />

NX12k<strong>63</strong><br />

Figure 8-49. Stall characteristics settings<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com