172 Description of Parameters Honeywell<br />

518 Acceleration/deceleration ramp speed scaling ratio<br />

between prohibit frequency limits 23457 (2.5.3, 2.5.7)<br />

Defines the acceleration/deceleration time when the output frequency is between the<br />

selected prohibit frequency range limits (parameters ID509 and ID510). The ramping<br />

speed (selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g.<br />

value 0.1 makes the acceleration time 10 times shorter than outside the prohibit<br />

frequency range limits.<br />

fout [Hz]<br />

Par. ID518 = 0,2<br />

Par. ID510<br />

(ID512; ID514)<br />

Par. ID509<br />

(ID511; ID513)<br />

Par. ID518 = 1,2<br />

NX12k81<br />

Time [s]<br />

Figure 8-46. Ramp speed scaling between prohibit frequencies<br />

519 Flux braking current 234567 (2.4.13)<br />

Defines the flux braking current value. The value setting range depends on the used<br />

application.<br />

520 Flux brake 234567 (2.4.12)<br />

Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases<br />

where additional brake resistors are not needed.<br />

When braking is needed, the frequency is reduced and the flux in the motor is increased,<br />

which in turn increases the motor's capability to brake. Unlike DC braking, the motor<br />

speed remains controlled during braking.<br />

The flux braking can be set ON or OFF.<br />

0 = Flux braking OFF<br />

1 = Flux braking ON<br />

Note: Flux braking converts the energy into heat at the motor, and should be used<br />

intermittently to avoid motor damage.<br />

521 Motor control mode 2 6 (2.6.12)<br />

With this parameter you can set another motor control mode. Which mode is used is<br />

determined with parameter ID164.<br />

For the selections, see parameter ID600.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com