Honeywell PID Control Application 53<br />

5.4.3 Input signals (Control keypad: Menu M2 G2.2)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.2.1 DIN2 function 0 13 1 319<br />

0=Not used<br />

1=External fault cc<br />

2=External fault oc<br />

3=Run enable<br />

4=Acc/Dec time selection<br />

5=CP: I/O terminal<br />

6=CP: Keypad<br />

7=CP: Fieldbus<br />

8=Forward/Reverse<br />

9=Jogging frequency (cc)<br />

10=Fault reset (cc)<br />

11=Acc/Dec prohibit (cc)<br />

12=DC braking command<br />

13=Motor pot. UP (cc)<br />

P2.2.2 DIN3 function 0 13 10 301<br />

See above except:<br />

13=Motor pot. DOWN (cc)<br />

P2.2.3 DIN5 function 0 13 9 330<br />

See above except:<br />

13=Enable PID reference<br />

2<br />

0=Direct PID output value<br />

1=AI1+PID output<br />

2=AI2+PID output<br />

P2.2.4<br />

3=AI3+PID output<br />

PID sum point<br />

0 7 0 376 4=AI4+PID output<br />

reference<br />

5=PID keypad+PID output<br />

6=Fieldbus+PID output<br />

(Process<strong>Data</strong>IN3)<br />

7=Mot.pot.+PID output<br />

P2.2.5<br />

P2.2.6<br />

P2.2.7<br />

P2.2.8<br />

P2.2.9<br />

I/O B reference<br />

selection<br />

Keypad control<br />

reference selection<br />

Fieldbus control<br />

reference selection<br />

Actual value<br />

selection<br />

Actual value 1<br />

selection<br />

0 7 1 343<br />

0=AI1<br />

1=AI2<br />

2=AI3<br />

3=AI4<br />

4=Keypad reference<br />

5=Fieldbus reference<br />

(FBSpeedReference)<br />

6=Motor potentiometer<br />

7=PID controller<br />

0 7 4 121 As in par. 2.2.5<br />

0 7 5 122 As in par. 2.2.5<br />

0 7 0 333<br />

0 10 2 334<br />

0=Actual value 1<br />

1=Actual 1 + Actual 2<br />

2=Actual 1 – Actual 2<br />

3=Actual 1 * Actual 2<br />

4=Max(Actual 1, Actual 2)<br />

5=Min(Actual 1, Actual 2)<br />

6=Mean(Actual1, Actual2)<br />

7=Sqrt (Act1) + Sqrt (Act2)<br />

0=Not used<br />

1=AI1 signal (c-board)<br />

2=AI2 signal (c-board)<br />

3=AI3<br />

4=AI4<br />

5=Fieldbus Process<strong>Data</strong>IN2<br />

6=Motor torque<br />

7=Motor speed<br />

8=Motor current<br />

9=Motor power<br />

10=Encoder frequency<br />

CP=control place, cc=closing contact oc=opening contact<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com