82 Multi-purpose Control Application Honeywell<br />

6.6.5.7 Analogue output 3 (Control keypad: Menu M2 G2.3.7)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.3.7.1<br />

Analogue output 3<br />

signal selection<br />

0 0.1 478<br />

P2.3.7.2<br />

Analogue output 3<br />

function<br />

0 15 5 479 See par. 2.3.5.2<br />

P2.3.7.3<br />

Analogue output 3<br />

filter time<br />

0,00 10,00 s 1,00 480 0=No filtering<br />

P2.3.7.4<br />

Analogue output 3<br />

0=Not inverted<br />

0 1 0 481<br />

inversion<br />

1=Inverted<br />

P2.3.7.5<br />

Analogue output 3<br />

0=0 mA<br />

0 1 0 482<br />

minimum<br />

1=4 mA<br />

P2.3.7.6<br />

Analogue output 3<br />

scale<br />

10 1000 % 100 483<br />

P2.3.7.7<br />

Analogue output 3<br />

offset<br />

-100,00 100,00 % 0,00 484<br />

Table 6-19. Analogue output 3 parameters, G2.3.7<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />