7<br />

80(110) Control keypad<br />

NOTE! There are some special functions that can be performed when in the M3<br />

menu:<br />

Select the keypad as the active control place by keeping the start button<br />

pushed down for 3 seconds when the motor is running. The keypad will become<br />

the active control place and the current frequency reference and direction will be<br />

copied to the keypad.<br />

Select the keypad as the active control place by keeping the stop button<br />

pushed down for 3 seconds when the motor is stopped. The keypad will become<br />

the active control place and the current frequency reference and direction will be<br />

copied to the keypad.<br />

Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by<br />

keeping the<br />

enter<br />

button pushed down for 3 seconds.<br />

Note that While in any other than M3 menu these functions will not work.<br />

If in a different menu other than M3 menu and try to start the motor by pressing the START button<br />

when the keypad is not selected as the active control place an error message Keypad Control NOT<br />

ACTIVE will be displayed.<br />

7.3.4 Active faults menu (M4)<br />

The Active faults menu can be entered from the Main menu by pushing the right arrow menu<br />

button when the location indication M4 is visible on the first line of the keypad display.<br />

When a fault brings the frequency drive to a stop, the location indication F1, the fault code, a short<br />

description of the fault and the fault type symbol (see Chapter 7.3.4.1) will appear on the display.<br />

In addition, the indication FAULT or ALARM (see Figure 7-1 or Chapter 7.1.1) is displayed and, in<br />

case of a FAULT, the red led on the keypad starts to blink. If several faults occur simultaneously,<br />

the list of active faults can be browsed with the Browser buttons.<br />

The memory of active faults can store the maximum of 10 faults in the order of appearance. The<br />

display can be cleared with the Reset button and the read-out will return to the same state it was<br />

before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset<br />

signal from the I/O terminal.<br />

Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the<br />

drive.<br />

Normal state,<br />

no faults:<br />

I/Oterm<br />

READY<br />

Active faults<br />

F0<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!