Honeywell Description of Parameters 1<strong>63</strong><br />

438 Reference fault or warning 67 (2.3.3.7, 2.3.1.7)<br />

Fault or warning depending on parameter ID700.<br />

439 Overtemperature warning 67 (2.3.3.8, 2.3.1.8)<br />

The heatsink temperature exceeds +70°C.<br />

440 Reverse 67 (2.3.3.9, 2.3.1.9)<br />

The Reverse command has been selected.<br />

441 Unrequested direction 67 (2.3.3.10, 2.3.1.10)<br />

Motor rotation direction is different from the requested one.<br />

442 At speed 67 (2.3.3.11, 2.3.1.11)<br />

The output frequency has reached the set reference.<br />

443 Jogging speed 67 (2.3.3.12, 2.3.1.12)<br />

Jogging speed selected.<br />

444 External control place 67 (2.3.3.13, 2.3.1.13)<br />

Control from I/O terminal selected (Menu M3; par. ID125).<br />

445 External brake control 67 (2.3.3.14, 2.3.1.14)<br />

External brake ON/OFF control with programmable delay. Used in applications where<br />

the mechanical brake is released when the brake coil is not energized.<br />

When using the Master Follower function, the follower drive will open the brake at the<br />

same time as the Master does even if the Follower's conditions for brake opening have<br />

not been met.<br />

446 External brake control, inverted 67 (2.3.3.15, 2.3.1.15)<br />

External brake ON/OFF control; Output active when brake control is OFF. Used in applications<br />

where the mechanical brake is in duty when voltage is not applied to the brake<br />

coil.<br />

When using the Master Follower function, the follower drive will open the brake at the<br />

same time as the Master does even if the Follower's conditions for brake opening have<br />

not been met.<br />

447 Output frequency limit 1 supervision 67 (2.3.3.16, 2.3.1.16)<br />

The output frequency goes outside the set supervision low limit/high limit (see<br />

parameters ID315 and ID316).<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!