198 Description of Parameters Honeywell<br />

1029 Autochange interval 7 (2.9.26)<br />

After the expiry of the time defined with this parameter, the autochange function takes<br />

place if the capacity used lies below the level defined with parameters ID1031 (Autochange<br />

frequency limit) and ID1030 (Maximum number of auxiliary drives). Should the<br />

capacity exceed the value of ID1031, the autochange will not take place before the capacity<br />

goes below this limit.<br />

• The time count is activated only if the Start/Stop request is active.<br />

• The time count is reset after the autochange has taken place.<br />

See Figure 8-64.<br />

1030 Maximum number of auxiliary drives 7 (2.9.27)<br />

1031 Autochange frequency limit 7 (2.9.28)<br />

These parameters define the level below which the capacity used must remain so that<br />

the autochange can take place.<br />

This level is defined as follows:<br />

• If the number of running auxiliary drives is smaller than the value of parameter<br />

ID1030 the autochange function can take place.<br />

• If the number of running auxiliary drives is equal to the value of parameter ID1030<br />

and the frequency of the controlled drive is below the value of parameter ID1031 the<br />

autochange can take place.<br />

• If the value of parameter ID1031 is 0.0 Hz, the autochange can take place only in<br />

rest position (Stop and Sleep) regardless of the value of parameter ID1030.<br />

Output<br />

frequency<br />

Par. ID1030 = 1<br />

Max.number of<br />

auxiliary drives<br />

Autochange moment<br />

Par. ID1031<br />

Autochange<br />

level, frequency<br />

Time<br />

Par. ID1029<br />

Autochange interval<br />

Par. ID1029<br />

Autochange interval<br />

Aux. drive 1<br />

control<br />

Aux. drive 2<br />

control<br />

Figure 8-64. Autochange interval and limits<br />

NX12k98.fh3<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!