78 Multi-purpose Control Application Honeywell<br />

6.6.5 Output signals<br />

6.6.5.1 Delayed digital output 1 (Keypad: Menu M2 G2.3.1)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.3.1.1<br />

Digital output 1<br />

Possible to invert with<br />

0 0.1 486<br />

signal selection<br />

ID1084 (NXP only)<br />

0=Not used<br />

1=Ready<br />

2=Run<br />

3=Fault<br />

4=Fault inverted<br />

5=FC overheat warning<br />

6=Ext. fault or warning<br />

7=Ref. fault or warning<br />

8=Warning<br />

9=Reverse<br />

10=Jogging spd selected<br />

11=At speed<br />

12=Mot. regulator active<br />

P2.3.1.2<br />

Digital output 1<br />

13=Freq. limit 1 superv.<br />

0 26 1 312<br />

function<br />

14=Freq. limit 2 superv.<br />

15=Torque limit superv.<br />

16=Ref. limit supervision<br />

17=External brake control<br />

18=I/O control place act.<br />

19=FC temp. limit superv.<br />

20=Reference inverted<br />

21=Ext. brake control<br />

inverted<br />

22=Therm. fault or warn.<br />

23=AI supervision<br />

24=Fieldbus input data 1<br />

25=Fieldbus input data 2<br />

26=Fieldbus input data 3<br />

P2.3.1.3<br />

Digital output 1 on<br />

delay<br />

0,00 320,00 s 0,00 487 0,00 = delay not in use<br />

P2.3.1.4<br />

Digital output 1 off<br />

delay<br />

0,00 320,00 s 0.00 488 0,00 = delay not in use<br />

Table 6-13. Delayed digital output 1 parameters, G2.3.1<br />

6.6.5.2 Delayed digital output 2 (Keypad: Menu M2 G2.3.2)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.3.2.1<br />

Digital output 2<br />

Possible to invert with<br />

0 0.1 489<br />

signal selection<br />

ID1084 (NXP only)<br />

P2.3.2.2<br />

Digital output 2<br />

function<br />

0 26 0 490 See par. 2.3.1.2<br />

P2.3.2.3<br />

Digital output 2 on<br />

delay<br />

0,00 320,00 s 0,00 491 0,00 = delay not in use<br />

P2.3.2.4<br />

Digital output 2 off<br />

delay<br />

0,00 320,00 s 0,00 492 0,00 = delay not in use<br />

Table 6-14. Delayed digital output 2 parameters, G2.3.2<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!