134 Description of Parameters Honeywell<br />

3 3-wire connection (pulse control):<br />

DIN1: closed contact = start pulse<br />

DIN2: open contact = stop pulse<br />

(DIN3 can be programmed for reverse command)<br />

See Figure 8-8.<br />

Output<br />

frequency<br />

Stop function<br />

(ID506)<br />

= coasting<br />

If Start and Stop pulses are<br />

simultaneous the Stop pulse<br />

overrides the Start pulse<br />

t<br />

REV<br />

DIN1<br />

Start<br />

DIN2<br />

Stop<br />

Figure 8-8. Start pulse/ Stop pulse.<br />

NX012K11<br />

The selections including the text 'Rising edge required to start' shall be used to<br />

exclude the possibility of an unintentional start when, for example, power is connected,<br />

re-connected after a power failure, after a fault reset, after the drive is stopped by Run<br />

Enable (Run Enable = False) or when the control place is changed. The Start/Stop<br />

contact must be opened before the motor can be started.<br />

Applications 2 and 4:<br />

4 DIN1: closed contact = start forward (Rising edge required to start)<br />

DIN2: closed contact = start reverse (Rising edge required to start)<br />

5 DIN1: closed contact = start (Rising edge required to start)<br />

open contact = stop<br />

DIN2: closed contact = reverse<br />

open contact = forward<br />

6 DIN1: closed contact = start (Rising edge required to start)<br />

open contact = stop<br />

DIN2: closed contact = start enabled<br />

open contact = start disabled and drive stopped if running<br />

(DIN3 can be programmed for reverse command)<br />

Application 3 and 6:<br />

4 DIN1: closed contact = start forward<br />

DIN2: closed contact = reference increases (motor potentiometer reference; this<br />

parameter is automatically set to 4 if par. ID117 is set to 3 or 4).<br />

5 DIN1: closed contact = start forward (Rising edge required to start)<br />

DIN2: closed contact = start reverse (Rising edge required to start)<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com