Honeywell Multi-step Speed Application 35<br />

4. MULTI-STEP SPEED <strong>CONTROL</strong> APPLICATION<br />

(Software ASFIFF04)<br />

4.1 Introduction<br />

Select the Multi-step Speed Control Application in menu M6 on page S6.2.<br />

The Multi-step Speed Control Application can be used in applications where fixed speeds are<br />

needed. Totally 15 + 2 different speeds can be programmed: one basic speed, 15 multi-step speeds<br />

and one jogging speed. The speed steps are selected with digital signals DIN3, DIN4, DIN5 and<br />

DIN6. If jogging speed is used, DIN3 can be programmed from fault reset to jogging speed select.<br />

The basic speed reference can be either voltage or current signal via analogue input terminals (2/3<br />

or 4/5). The other one of the analogue inputs can be programmed for other purposes.<br />

• All outputs are freely programmable.<br />

Additional functions:<br />

• Programmable Start/Stop and Reverse signal logic<br />

• Reference scaling<br />

• One frequency limit supervision<br />

• Second ramps and S-shape ramp programming<br />

• Programmable start and stop functions<br />

• DC-brake at stop<br />

• One prohibit frequency area<br />

• Programmable U/f curve and switching frequency<br />

• Autorestart<br />

• Motor thermal and stall protection: Programmable action; off, warning, fault<br />

The parameters of the Multi-Step Speed Control Application are explained in Chapter 8 of this<br />

manual. The explanations are arranged according to the individual ID number of the parameter.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />