Honeywell Description of Parameters 127<br />

Speed<br />

Multi-step speed Multi-step speed Multi-step speed Multi-step speed<br />

sel. 1 (DIN4) sel. 2 (DIN5) sel. 3 (DIN6) sel. 4 (DIN3)<br />

Basic speed 0 0 0 0<br />

P2.1.17 (3) 1 1 0 0<br />

P2.1.18 (4) 0 0 1 0<br />

P2.1.19 (5) 1 0 1 0<br />

P2.1.20 (6) 0 1 1 0<br />

P2.1.21 (7) 1 1 1 0<br />

Table 8-4. Preset speeds 3 to 7<br />

131 I/O frequency reference selection, place B 3 (2.1.12)<br />

See the values of the parameter ID117 above.<br />

132 PID controller D-time 57 (2.1.14)<br />

The parameter ID132 defines the derivation time of the PID controller. If this parameter<br />

is set to 1,00 second a change of 10% in the error value during 1.00 s causes the<br />

controller output to change by 10.00%. If the parameter value is set to 0.00 s the PID<br />

controller will operate as PI controller.<br />

See examples below.<br />

Example 1:<br />

In order to reduce the error value to zero, with the given values, the frequency drive<br />

output behaves as follows:<br />

Given values:<br />

Par. 2.1.12, P = 0%<br />

Par. 2.1.13, I-time = 1.00 s<br />

Par. 2.1.14, D-time = 0.00 s<br />

Min freq. = 0 Hz<br />

Error value (setpoint – process value) = 10.00% Max freq. = 50 Hz<br />

In this example, the PID controller operates practically as I-controller only.<br />

According to the given value of parameter 2.1.13 (I-time), the PID output increases by 5<br />

Hz (10% of the difference between the maximum and minimum frequency) every second<br />

until the error value is 0.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!