86 Multi-purpose Control Application Honeywell<br />

6.6.8.1 <strong>NXS</strong> drives: Closed Loop parameters (Control keypad: Menu M2 G2.6.17)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.6.17.1<br />

Magnetizing<br />

current<br />

0,00 100,00 A 0,00 612 If zero internally calculated<br />

P2.6.17.2<br />

Speed control P<br />

gain<br />

1 1000 30 613<br />

P2.6.17.3<br />

Speed control I<br />

Negative value uses 0,1 ms<br />

-32000 32000 ms 100,0 614<br />

time<br />

accuracy instead of 1 ms<br />

P2.6.17.5<br />

Acceleration<br />

compensation<br />

0,00 300,00 s 0,00 626<br />

P2.6.17.6 Slip adjust 0 500 % 75 619<br />

P2.6.17.7<br />

Magnetizing<br />

current at start<br />

0,00 I L A 0,00 627<br />

P2.6.17.8<br />

Magnetizing time<br />

at start<br />

0 32000 ms 0 628<br />

P2.6.17.9<br />

0-speed time at<br />

start<br />

0 32000 ms 100 615<br />

P2.6.17.10<br />

0-speed time at<br />

stop<br />

0 32000 ms 100 616<br />

P2.6.17.11 Start-up torque 0 3 0 621<br />

0=Not used<br />

1=Torque memory<br />

2=Torque reference<br />

3=Start-up torque fwd/rev<br />

P2.6.17.12<br />

Start-up torque<br />

FWD<br />

–300,0 300,0 % 0,0 <strong>63</strong>3<br />

P2.6.17.13<br />

Start-up torque<br />

REV<br />

–300,0 300,0 % 0,0 <strong>63</strong>4<br />

P2.6.17.15 Encoder filter time 0,0 100,0 ms 0,0 618<br />

P2.6.17.17<br />

Current control<br />

P gain<br />

0,00 100,00 % 40,00 617<br />

Table 6-23. Closed Loop parameters, <strong>NXS</strong> drives<br />

6.6.8.2 <strong>NXS</strong> drives: Identification (Control keypad: Menu M2 G2.6.19)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.6.19.23 Speed step -50,0 50,0 0,0 0,0<br />

125<br />

2<br />

NCDrive speed tuning<br />

P2.6.19.24 Torque step -100,0 100,0 0,0 0,0<br />

125<br />

3<br />

NCDrive torque tuning<br />

Table 6-24. Identification parameters, <strong>NXS</strong> drives<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com