164 Description of Parameters Honeywell<br />

448 Output frequency limit 2 supervision 67 (2.3.3.17, 2.3.1.17)<br />

The output frequency goes outside the set supervision low limit/high limit (see<br />

parameters ID346 and ID347)<br />

449 Reference limit supervision 67 (2.3.3.18, 2.3.1.18)<br />

Active reference goes beyond the set supervision low limit/high limit (see parameters<br />

ID350 and ID351).<br />

450 Temperature limit supervision 67 (2.3.3.19, 2.3.1.19)<br />

Frequency drive heatsink temperature goes beyond the set supervision limits (see<br />

parameters ID354 and ID355).<br />

451 Torque limit supervision 67 (2.3.3.20, 2.3.1.20)<br />

The motor torque goes beyond the set supervision limits (see parameters ID348 and<br />

ID349).<br />

452 Motor thermal protection 67 (2.3.3.21, 2.3.1.21)<br />

Motor thermistor initiates a overtemperature signal which can be led to a digital output.<br />

NOTE: This parameter will not work unless you have OPT-A3 or OPT-B2 (thermistor<br />

relay board) connected.<br />

454 Motor regulator activation 67 (2.3.3.23, 2.3.1.23)<br />

Overvoltage or overcurrent regulator has been activated.<br />

455 Fieldbus input data 1 (FBFixedControlWord, bit 3) 67 (2.3.3.24, 2.3.1.24)<br />

456 Fieldbus input data 2 (FBFixedControlWord, bit 4) 67 (2.3.3.25, 2.3.1.25)<br />

457 Fieldbus input data 3 (FBFixedControlWord, bit 5) 67 (2.3.3.26, 2.3.1.26)<br />

The data from the fieldbus (FBFixedControlWord) can be led to frequency drive digital<br />

outputs.<br />

458 Autochange 1/Auxiliary drive 1 control 7 (2.3.1.27)<br />

Control signal for autochange/auxiliary drive 1.<br />

Default programming: B.1<br />

459 Autochange 2/Auxiliary drive 2 control 7 (2.3.1.28)<br />

Control signal for autochange/auxiliary drive 2.<br />

Default programming: B.2<br />

460 Autochange 3/Auxiliary drive 3 control 7 (2.3.1.29)<br />

Control signal for autochange/auxiliary drive 3. If three (or more) auxiliary drives are<br />

used, we recommend to connect nr 3, too, to a relay output. Since the OPT-A2 board<br />

only has two relay outputs it is advisable to purchase an I/O expander board with extra<br />

relay outputs (e.g. OPT-B5).<br />

Automation and Control Solutions<br />

Honeywell<br />