Honeywell Multi-purpose Control Application 83<br />

6.6.6 Drive control parameters (Control keypad: Menu M2 G2.4)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.4.1 Ramp 1 shape 0,0 10,0 s 0,1 500<br />

0=Linear<br />

>0=S-curve ramp time<br />

P2.4.2 Ramp 2 shape 0,0 10,0 s 0,0 501<br />

0=Linear<br />

>0=S-curve ramp time<br />

P2.4.3 Acceleration time 2 0,1 3000,0 s 10,0 502<br />

P2.4.4 Deceleration time 2 0,1 3000,0 s 10,0 503<br />

P2.4.5 Brake chopper 0 4 0 504<br />

0=Disabled<br />

1=Used when running<br />

2=External brake chopper<br />

3=Used when<br />

stopped/running<br />

4=Used when running (no<br />

testing)<br />

P2.4.6 Start function 0 1 0 505<br />

0=Ramp<br />

1=Flying start<br />

P2.4.7 Stop function 0 3 0 506<br />

0=Coasting<br />

1=Ramp<br />

2=Ramp+Run enable<br />

coast<br />

3=Coast+Run enable<br />

ramp<br />

P2.4.8 DC braking current 0 I L A 0,7 x I H 507<br />

P2.4.9<br />

DC braking time<br />

at stop<br />

0,00 600,00 s 0,00 508 0=DC brake is off at stop<br />

P2.4.10<br />

Frequency to start<br />

DC braking during<br />

ramp stop<br />

0,10 10,00 Hz 1,50 515<br />

P2.4.11<br />

DC braking time<br />

at start<br />

0,00 600,00 s 0,00 516 0=DC brake is off at start<br />

P2.4.12 Flux brake 0 1 0 520<br />

P2.4.13 Flux braking current 0 I L A I H 519<br />

NXP drives only<br />

P2.4.15<br />

DC-brake current at<br />

108<br />

0 I<br />

stop<br />

L A 0,1 x I H<br />

0<br />

P2.4.16 Inching reference 1 -320,00 320,00 Hz 2,00<br />

123<br />

9<br />

P2.4.17 Inching reference 2 -320,00 320,00 Hz -2,00<br />

124<br />

0<br />

P2.4.18 Inching ramp 0,1 3200,0 s 1,0 533<br />

P2.4.21<br />

Emergency stop<br />

127<br />

0 1 0<br />

mode<br />

6<br />

P2.4.22 Control options 0 65536 0<br />

108<br />

4<br />

Table 6-20. Drive control parameters, G2.4<br />

0=Off<br />

1=On<br />

0=Coasting<br />

1=Ramp<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!