Honeywell Description of Parameters 133<br />

300 Start/Stop logic selection 2346 (2.2.1, 2.2.1.1)<br />

0 DIN1: closed contact = start forward<br />

DIN2: closed contact = start reverse<br />

FWD<br />

Output<br />

frequency<br />

Stop function<br />

(ID506)<br />

= coasting<br />

t<br />

REV<br />

DIN1<br />

DIN2<br />

Figure 8-6. Start forward/Start reverse<br />

1 2 3<br />

NX12K09<br />

The first selected direction has the highest priority.<br />

When the DIN1 contact opens the direction of rotation starts the change.<br />

If Start forward (DIN1) and Start reverse (DIN2) signals are active simultaneously<br />

the Start forward signal (DIN1) has priority.<br />

1 DIN1: closed contact = start open contact = stop<br />

DIN2: closed contact = reverse open contact = forward<br />

See below.<br />

FWD<br />

Output<br />

frequency<br />

Stop function<br />

(ID506)<br />

= coasting<br />

t<br />

REV<br />

DIN1<br />

DIN2<br />

Figure 8-7. Start, Stop, Reverse<br />

NX12K10<br />

2 DIN1: closed contact = start open contact = stop<br />

DIN2: closed contact = start enabled open contact = start disabled and drive stopped<br />

if running<br />

(DIN3 can be programmed for reverse command)<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!