Honeywell Multi-step Speed Application 43<br />

P2.3.13<br />

P2.3.14<br />

P2.3.15<br />

P2.3.16<br />

Output frequency<br />

limit 2;<br />

Supervision value<br />

Torque limit<br />

supervision function<br />

Torque limit<br />

supervision value<br />

Reference limit<br />

supervision function<br />

0,00 320,00 Hz 0,00 347<br />

0 2 0 348<br />

-300,0 300,0 % 100,0 349<br />

0 2 0 350<br />

0=No<br />

1=Low limit<br />

2=High limit<br />

0=No<br />

1=Low limit<br />

2=High limit<br />

P2.3.17<br />

Reference limit<br />

supervision value<br />

0,0 100,0 % 0,0 351<br />

P2.3.18<br />

External brake Offdelay<br />

0,0 100,0 s 0,5 352<br />

P2.3.19<br />

External brake Ondelay<br />

0,0 100,0 s 1,5 353<br />

P2.3.20<br />

Frequency drive<br />

temperature limit<br />

supervision<br />

0 2 0 354<br />

0=No<br />

1=Low limit<br />

2=High limit<br />

Frequency drive<br />

P2.3.21 temperature limit -10 100 °C 40 355<br />

value<br />

P2.3.22<br />

Analogue output 2<br />

TTF programming method<br />

0 0.1 471<br />

signal selection<br />

used. See page 65.<br />

P2.3.23<br />

Analogue output 2<br />

function<br />

0 8 4 472 As parameter 2.3.2<br />

P2.3.24<br />

Analogue output 2<br />

filter time<br />

0,00 10,00 s 1,00 473 0=No filtering<br />

P2.3.25<br />

Analogue output 2<br />

0=Not inverted<br />

0 1 0 474<br />

inversion<br />

1=Inverted<br />

P2.3.26<br />

Analogue output 2<br />

0=0 mA<br />

0 1 0 475<br />

minimum<br />

1=4 mA<br />

P2.3.27<br />

Analogue output 2<br />

scaling<br />

10 1000 % 100 476<br />

Table 4-5. Output signals, G2.3<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com