22(110) <strong>Technical</strong> data<br />

4.4 <strong>Technical</strong> data<br />

Mains<br />

connection<br />

Motor<br />

connection<br />

Control<br />

characteristics<br />

Ambient<br />

conditions<br />

Input voltage U in<br />

Input frequency<br />

Connection to mains<br />

Output voltage<br />

Continuous output current<br />

Starting torque<br />

Peak current<br />

Output frequency<br />

Frequency resolution<br />

Control method<br />

Switching frequency<br />

(see parameter 2.6.9)<br />

Frequency reference<br />

Analogue input<br />

Panel reference<br />

Field weakening point<br />

Acceleration time<br />

Deceleration time<br />

Braking torque<br />

Ambient operating<br />

temperature<br />

Storage temperature<br />

Relative humidity<br />

Air quality:<br />

- chemical vapours<br />

- mechanical particles<br />

Altitude<br />

208…240V; 380…500V; 525…690V; –10%…+10%<br />

45…66 Hz<br />

Once per minute or less (normal case)<br />

0—U in<br />

I H : Ambient temperature max. +122ºF (50°C),<br />

overload 1.5 x I H (1 min./10 min.)<br />

I L : Ambient temperature max. +104°F (40°C),<br />

overload 1.1 x I L (1 min./10 min.)<br />

I S for two seconds, torque motor dependent<br />

I S for 2 s every 20 s<br />

0…320 Hz (<strong>NXS</strong>); 7200 Hz (Special)<br />

0.01 Hz (<strong>NXS</strong>); Application dependent (NXP)<br />

Frequency control U/f<br />

Open Loop Sensorless Vector Control<br />

Closed Loop Frequency Control<br />

Closed Loop Vector Control (NXP only)<br />

NX B/ Up to and including NX_0061:<br />

NX A: 1…16 kHz; Factory default 10 kHz<br />

From NX_0072:<br />

1…10 kHz; Factory default 3.6 kHz<br />

NX C: 1…6 kHz; Factory default 1.5 kHz<br />

Resolution 0.1% (10-bit), accuracy ±1%<br />

Resolution 0.01 Hz<br />

8…320 Hz<br />

0.1…3000 sec<br />

0.1…3000 sec<br />

DC brake: 30% * T N (without brake option)<br />

–14°F (-10°C) (no frost)…+122°F (50°C): I H<br />

–14°F (-10°C) (no frost)…+104°F (40°C): I L<br />

–104°F…+158°F<br />

0 to 95% RH, non-condensing, non-corrosive,<br />

no dripping water<br />

IEC 721-3-3, unit in operation, class 3C2<br />

IEC 721-3-3, unit in operation, class 3S2<br />

100% load capacity (no derating) up to 3147 feet<br />

1-% derating for each 327 ft above 3147 ft.; max. 9843 ft<br />

Vibration<br />

5…150 Hz<br />

EN50178/EN60068-2-6 Displacement amplitude 0,04 in (peak) at 3…15.8 Hz<br />

Max acceleration amplitude 1 G at 15.8…150 Hz<br />

Shock<br />

UPS Drop Test (for applicable UPS weights)<br />

IEC50178, IEC60068-2-27 Storage and shipping: max 15 G, 11 ms (in package)<br />

Enclosure class<br />

IP21/NEMA1 standard in entire kW/HP range<br />

IP54/NEMA12 option in entire kW/HP range<br />

Note! Keypad installation required for IP54<br />

Table 4-3. <strong>Technical</strong> data (continues on next page)<br />

4<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!