<strong>Technical</strong> data 17(110)<br />

4.2 Power ratings<br />

4.2.1 NX_5 – Mains voltage 380—500 V<br />

Low overload = 150% starting torque, 2 sec/20 sec, 110% overloadability, 1 min/10 min<br />

Following continuous operation at rated output current, 110% rated output current (IL)<br />

for 1 min, followed by a period of load current less than rated current, and of such<br />

duration that the r.m.s output current, over the duty cycle, does not exceed rated output<br />

current (IL)<br />

High overload = 200% starting torque, 2 sec/20 sec, 150% overloadability, 1 min/10 min<br />

Following continuous operation at rated output current, 150 % rated output current (IH)<br />

for 1 min, followed by a period of load current less than rated current, and of such<br />

duration that the r.m.s output current, over the duty cycle, does not exceed rated output<br />

current (IH)<br />

All sizes up to and including FR9 are wall mounted available with NEMA1 enclosure and<br />

NEMA12 as option. All sizes above and including FR10 are standalone NEMA 1 NXP units.<br />

For single phase input connections, ratings and wiring instructions can be found in 6.2.1<br />

Mains voltage 380-500 V, NEMA 1/12, EMC-level H<br />

Frequency Motor shaft power (500V) and current<br />

drive type Low overload High overload<br />

P [Hp]<br />

(500V)<br />

I(L)<br />

P [Hp]<br />

(500V)<br />

I(H)<br />

I(max)<br />

Size / prot. FR/IP<br />

Dimensions<br />

WxHxD<br />

(in)<br />

Weight<br />

(lb)<br />

NX_ 0015 A 1.5 3.3 1 2.2 4.4 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0020 A 2 4.3 1.5 3.3 6.2 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0030 A 3 5.6 2 4.3 8.6 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0040 A 4 7.6 3 5.6 10.8 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0050 A 5 9 4 7.6 14 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0075 A 7.5 12 5 9 18 FR4/NEMA 1/12 5.0x11.5x7.5 11.02<br />

NX_ 0100 A 10 16 7.5 12 24 FR5/NEMA 1/12 5.7x15.4x8.4 17.86<br />

NX_ 0150 A 15 23 10 16 32 FR5/NEMA 1/12 5.7x15.4x8.4 17.86<br />

NX_ 0200 A 20 31 15 23 46 FR5/NEMA 1/12 5.7x15.4x8.4 17.86<br />

NX_ 0250 A 25 38 20 31 62 FR6/NEMA 1/12 7.7x20.4x9.3 40.8<br />

NX_ 0300 A 30 46 25 38 76 FR6/NEMA 1/12 7.7x20.4x9.3 40.8<br />

NX_ 0400 A 40 61 30 46 92 FR6/NEMA 1/12 7.7x20.4x9.3 40.8<br />

NX_ 0500 A 50 72 40 61 122 FR7/NEMA 1/12 9.3x23.3x10.1 77.2<br />

NX_ 0600 A 60 87 50 72 144 FR7/NEMA 1/12 9.3x23.3x10.1 77.2<br />

NX_ 0750 A 75 105 60 87 174 FR7/NEMA 1/12 9.3x23.3x10.1 77.2<br />

NX_ 1000 A 100 140 75 105 210 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 1250 A 125 170 100 140 280 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 1500 A 150 205 125 170 336 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 2000 A 200 261 150 205 349 FR9/NEMA 1/12 18.9x45.3x14.3 321.9<br />

NX_ 2500 A 250 300 200 245 444 FR9/NEMA 1/12 18.9x45.3x14.3 321.9<br />

NXP 3000 A 300 385 250 300 540 FR10/NEMA1 23.6x89.6x23.6 661.1<br />

NXP 3500 A 350 460 300 385 693 FR10/NEMA1 23.6x89.6x23.6 661.1<br />

NXP 4500 A 450 520 350 460 828 FR10/NEMA1 23.6x89.6x23.6 661.1<br />

NXP 5000 A 500 590 450 520 936 FR11/NEMA1 31.6x79.4x23.6 815.7<br />

NXP 5500 A 550 650 500 590 1062 FR11/NEMA1 31.6x79.4x23.6 815.7<br />

NXP 6000 A 600 730 550 650 1170 FR11/NEMA1 31.6x79.4x23.6 815.7<br />

NXP 6500 A 650 820 600 730 1314 FR12/NEMA1 47.6x 79.4x 23.6 1322.8<br />

NXP 7000 A 700 920 650 820 1476 FR12/NEMA1 47.6x 79.4x 23.6 1322.8<br />

NXP 8000 A 800 1030 700 920 1654 FR12/NEMA1 47.6x 79.4x 23.6 1322.8<br />

Table 4-1. Power ratings and dimensions of the NX, supply voltage 380—500V.<br />

Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is<br />

equal to or less than the factory default.<br />

Note: The rated currents for FR10 to FR12 are all valid at an ambient temperature of 104 °F.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com<br />

4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!