Honeywell Description of Parameters 203<br />

1209 Input switch acknowledgement 6 (2.2.7.32)<br />

Select the digital input to acknowledge the status of the input switch. The input switch<br />

is normally a switch fuse unit or main contactor with which the power is fed to the<br />

drive. If the input switch acknowledgement is missing, the drive trips at Input switch open<br />

fault (F64). The parameter is available for NXP drives only.<br />

1210 External brake acknowledgement 6 (2.2.7.24)<br />

If no acknowledgement is received within given time the drive will generate a brake fault.<br />

The parameter is available for NXP drives only.<br />

1213 Emergency stop 6 (2.2.7.30)<br />

Select the digital input to activate the emergency stop input to the drive. When the digital<br />

input is down the drive stops as per the parameter definition of ID1276 Emergency stop<br />

mode. The parameter is available for NXP drives only.<br />

1218 DC ready pulse 6 (2.3.3.29)<br />

Charge DC. Used to charge the inverter drive through OEVA type of input switch. When<br />

the DC link voltage is above the charging level a 2-second pulse train is generated to<br />

close the input switch. The pulse train is OFF when the input switch acknowledgement<br />

goes high. The parameter is available for NXP drives only.<br />

1239 Inching reference 1 6 (2.4.16)<br />

1240 Inching reference 2 6 (2.4.17)<br />

These parameters define the frequency reference when inching is activated.<br />

The parameter is available for NXP drives only.<br />

1241 Speed share 6 (2.11.5)<br />

Defines the percentage for final speed reference from received speed reference.<br />

1244 Torque reference filtering time 6 (2.10.10)<br />

1248 Load share 6 (2.11.6)<br />

Defines the percentage for final torque reference from received torque reference.<br />

1250 Flux reference 6 (2.6.27.32)<br />

Defines how much magnetization current will be used.<br />

1252 Speed step 6 (2.6.19.23, 2.6.29.24)<br />

NCDrive parameter to help adjusting the speed controller.<br />

1253 Torque step 6 (2.6.19.24, 2.6.29.25)<br />

NCDrive parameter to help adjusting the torque controller.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!