Honeywell Description of Parameters 187<br />

728 4mA reference fault: preset frequency reference 234567 (2.7.2)<br />

If the value of parameter ID700 is set to 3 and the 4mA fault occurs then the frequency<br />

reference to the motor is the value of this parameter.<br />

730 Input phase supervision 234567 (2.7.4)<br />

0 = No response<br />

1 = Warning<br />

2 = Fault, stop mode after fault according to ID506<br />

3 = Fault, stop mode after fault always by coasting<br />

The input phase supervision ensures that the input phases of the frequency drive have<br />

an approximately equal current.<br />

731 Automatic restart 1 (2.20)<br />

The Automatic restart is taken into use with this parameter.<br />

0 = Disabled<br />

1 = Enabled<br />

The function resets the following faults (max. three times) (see the product's user's<br />

manual:<br />

• Overcurrent (F1)<br />

• Overvoltage (F2)<br />

• Undervoltage (F9)<br />

• Frequency drive overtemperature (F14)<br />

• Motor overtemperature (F16)<br />

• Reference fault (F50)<br />

732 Response to thermistor fault 234567 (2.7.21)<br />

0 = No response<br />

1 = Warning<br />

2 = Fault, stop mode after fault according to ID506<br />

3 = Fault, stop mode after fault always by coasting<br />

Setting the parameter to 0 will deactivate the protection.<br />

733 Response to fieldbus fault 234567 (2.7.22)<br />

Set here the response mode for the fieldbus fault if a fieldbus board is used. For more<br />

information, see the respective Fieldbus Board <strong>Manual</strong>.<br />

See parameter ID732.<br />

734 Response to slot fault 234567 (2.7.23)<br />

Set here the response mode for a board slot fault due to missing or broken board.<br />

See parameter ID732.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!