126 Description of Parameters Honeywell<br />

121 Keypad frequency reference selection 234567 (2.1.12, 2.1.13,<br />

2.2.6, 2.2.1.2)<br />

Defines which frequency reference source is selected when controlled from the keypad.<br />

Applic. 2–4 5 6 7<br />

Sel.<br />

0<br />

Analogue volt.ref. Analogue volt.ref. Analogue volt.ref. Analogue volt.ref.<br />

Terminals 2–3 Terminals 2–3 Terminals 2–3 Terminals 2–3<br />

1<br />

Analogue curr.ref. Analogue curr.ref. Analogue curr.ref. Analogue curr.ref.<br />

Terminals 4–5 Terminals 4–5 Terminals 4–5 Terminals 4–5<br />

2<br />

Keypad reference<br />

(Menu M3)<br />

AI3 AI1+AI2 AI3<br />

3<br />

Fieldbus<br />

reference*<br />

AI4 AI1–AI2 AI4<br />

4<br />

Keypad reference<br />

Keypad reference<br />

AI2–AI1<br />

(Menu M3)<br />

(Menu M3)<br />

5<br />

Fieldbus<br />

Fieldbus<br />

AI1*AI2<br />

reference*<br />

reference*<br />

6 Potentiometer ref. AI1 joystick Potentiometer ref.<br />

7 PID controller ref. AI2 joystick PID controller ref.<br />

8<br />

Keypad reference<br />

(Menu M3)<br />

9<br />

Fieldbus<br />

reference*<br />

Table 8-3. Selections for parameter ID121<br />

*FBSpeedReference<br />

122 Fieldbus frequency reference selection 234567 (2.1.13, 2.1.14, 2.2.7, 2.2.1.3)<br />

Defines which frequency reference source is selected when controlled from the fieldbus.<br />

For selections in different applications, see ID121.<br />

124 Jogging speed reference 34567 (2.1.14, 2.1.15, 2.1.19)<br />

Defines the jogging speed selected with the DIN3 digital input which can be programmed<br />

for Jogging speed. See parameter ID301.<br />

Parameter value is automatically limited between minimum and maximum frequency<br />

(ID's 101 and 102).<br />

126 Preset speed 3 46 (2.1.17)<br />

127 Preset speed 4 46 (2.1.18)<br />

128 Preset speed 5 46 (2.1.19)<br />

129 Preset speed 6 46 (2.1.20)<br />

130 Preset speed 7 46 (2.1.21)<br />

Parameter values define the Multi-step speeds selected with the DIN3, DIN4, DIN5 and<br />

DIN6 digital inputs. See also parameter ID’s 105 and 106.<br />

Parameter value is automatically limited between minimum and maximum frequency<br />

(ID's 101 and 102).<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com