Honeywell Description of Parameters 139<br />

311 Analogue output scale 234567 (2.3.6, 2.3.5.6, 2.3.3.6)<br />

Scaling factor for analogue output.<br />

Signal<br />

Output frequency<br />

Freq. Reference<br />

Motor speed<br />

Output current<br />

Motor torque<br />

Max. value of the signal<br />

Max frequency (par.ID102)<br />

Max frequency (par.ID102)<br />

Motor nom. speed<br />

1xn mMotor<br />

Motor nom. current 1xI nMotor<br />

Motor nom. torque<br />

1xT nMotor<br />

Motor power Motor nom. power 1xP nMotor<br />

Motor voltage 100% x U nmotor<br />

DC-link voltage 1000 V<br />

PI-ref. value 100% x ref. value max.<br />

PI act. value 1 100% x actual value max.<br />

PI act. value 2 100% x actual value max.<br />

PI error value 100% x error value max.<br />

PI output<br />

100% x output max.<br />

Table 8-7. Analogue output scaling<br />

Analogue<br />

output<br />

current<br />

20 mA<br />

12 mA<br />

10 mA<br />

ID310 = 1<br />

4 mA<br />

ID310 = 0<br />

0 mA<br />

0<br />

ID311 =<br />

200%<br />

0.5<br />

ID311 =<br />

100%<br />

Figure 8-15. Analogue output scaling<br />

Max. value of signal<br />

selected by ID307<br />

1.0<br />

NX12K18<br />

ID311 =<br />

50%<br />

312 Digital output function 23456 (2.3.7, 2.3.1.2)<br />

313 Relay output 1 function 2345 (2.3.8, 2.3.1.3)<br />

314 Relay output 2 function 2345 (2.3.9)<br />

Setting value<br />

Signal content<br />

0 = Not used Out of operation<br />

Digital output DO1 sinks the current and<br />

programmable relay (RO1, RO2) is activated when:<br />

1 = Ready The frequency drive is ready to operate<br />

2 = Run The frequency drive operates (motor is running)<br />

3 = Fault A fault trip has occurred<br />

4 = Fault inverted A fault trip not occurred<br />

5 = NX overheat warning The heat-sink temperature exceeds +70°C<br />

6 = External fault or warning Fault or warning depending on par. ID701<br />

7 = Reference fault or warning<br />

Fault or warning depending on par. ID700<br />

- if analogue reference is 4—20 mA and signal is