Cabling and connections 61(110)<br />

6.2.1 <strong>NXS</strong> and NXP single phase input applications 380-500 VAC<br />

Power Ratings<br />

Overload = 200% starting torque, 2 sec/20 sec, 150% overloadability, 1 min/10 min<br />

Following continuous operation at rated output current, 150 % rated output current for 1 min, followed by<br />

a period of load current less than rated current, and of such duration that the r.m.s output current, over<br />

the duty cycle, does not exceed rated output current<br />

Mains voltage 380-500 V, NEMA 1/12, Single Phase Input<br />

Frequency MOTOR SHAFT POWER (480V) AND CURRENT<br />

converter P [Hp] I [A] Size / prot. Dimensions Weight<br />

type (480V) W x H x D (in) (lb)<br />

NX_ 0015 A 0,5 1,1 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0020 A 0,75 1,7 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0030 A 1 2,2 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0040 A 1,5 3 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0050 A 2 3,8 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0075 A 2 4,5 FR4/NEMA 1/12 5.04x11.5x7.48 11.02<br />

NX_ 0100 A 4 6 FR5/NEMA 1/12 5.67x15.4x8.43 17.86<br />

NX_ 0150 A 5 8 FR5/NEMA 1/12 5.67x15.4x8.43 17.86<br />

NX_ 0200 A 7,5 11 FR5/NEMA 1/12 5.67x15.4x8.43 17.86<br />

NX_ 0250 A 10 16 FR6/NEMA 1/12 7.68x20.4x9.33 40.79<br />

NX_ 0300 A 15 21 FR6/NEMA 1/12 7.68x20.4x9.33 40.79<br />

NX_ 0400 A 15 23 FR6/NEMA 1/12 7.68x20.4x9.33 40.79<br />

NX_ 0500 A 20 31 FR7/NEMA 1/12 9.33x23.3x10.1 77.16<br />

NX_ 0600 A 25 36 FR7/NEMA 1/12 9.33x23.3x10.1 77.16<br />

NX_ 0750 A 30 40 FR7/NEMA 1/12 9.33x23.3x10.1 77.16<br />

NX_ 1000 A 40 53 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 1250 A 50 70 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 1500 A 60 85 FR8/NEMA 1/12 11.2x28.4x11.3 127.9<br />

NX_ 2000 A 75 103 FR9/NEMA 1/12 18.9x45.3x14.3 321.9<br />

NX_ 2500 A 100 124 FR9/NEMA 1/12 18.9x45.3x14.3 321.9<br />

NXP 3000 A 125 156 FR10/NEMA 1 23.6x89.6x23.6 661.1<br />

NXP 3500 A 150 193 FR10/NEMA 1 23.6x89.6x23.6 661.1<br />

NXP 4500 A 150 230 FR10/NEMA 1 23.6x89.6x23.6 661.1<br />

NXP 5000 A 200 260 FR11/NEMA 1 31.6x79.4x23.6 815.7<br />

NXP 5500 A 250 302 FR11/NEMA 1 31.6x79.4x23.6 815.7<br />

NXP 6000 A 250 325 FR11/NEMA 1 31.6x79.4x23.6 815.7<br />

NXP 6500 A 300 365 FR12/NEMA 1 47.6x 79.4x 23.6 1322.8<br />

NXP 7000 A 350 414 FR12/NEMA 1 47.6x 79.4x 23.6 1322.8<br />

NXP 8000 A 350 460 FR12/NEMA 1 47.6x 79.4x 23.6 1322.8<br />

Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is<br />

equal to or less than the factory default.<br />

Input connections in single phase application<br />

L1 L2 L3<br />

L<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com<br />

N<br />