176 Description of Parameters Honeywell<br />

620 Load drooping 23456 (2.6.12, 2.6.15)<br />

The drooping function enables speed drop as a function of load. This parameter sets<br />

that amount corresponding to the nominal torque of the motor.<br />

621 CL: Startup torque 23456 (2.6.4.11, 2.6.27.11)<br />

Choose here the startup torque.<br />

Torque Memory is used in crane applications. Startup Torque FWD/REV can be used in<br />

other applications to help the speed controller. See chapter 9.2.<br />

0 = Not Used<br />

1 = TorqMemory<br />

2 = Torque Ref<br />

3 = Torq.Fwd/Rev<br />

626 CL: Acceleration compensation 23456 (2.6.4.5, 2.6.27.5)<br />

Sets the inertia compensation to improve speed response during acceleration and<br />

deceleration. The time is defined as acceleration time to nominal speed with nominal<br />

torque. This parameter is active also in advanced open loop mode.<br />

627 CL: Magnetizing current at start 23456 (2.6.4.7, 2.6.27.7)<br />

628 CL: Magnetizing time at start 23456 (2.6.4.8, 2.6.27.8)<br />

Set here the rise time of magnetizing current.<br />

<strong>63</strong>1 Identification 23456 (2.6.13, 2.6.16)<br />

Identification Run is a part of tuning the motor and the drive specific parameters. It is a<br />

tool for commissioning and service of the drive with the aim to find as good parameter<br />

values as possible for most drives. The automatic motor identification calculates or<br />

measures the motor parameters that are needed for optimum motor and speed control.<br />

0 = No action<br />

No identification requested.<br />

1 = Identification without motor run<br />

The drive is run without speed to identify the motor parameters. The motor is supplied<br />

with current and voltage but with zero frequency.<br />

2 = Identification with motor run<br />

The drive is run with speed to identify the motor parameters.<br />

Note: It is recommended to do the this identification test with no load on the motor for<br />

best results.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!