Honeywell Description of Parameters 145<br />

332 PID controller reference signal (Place A) 57 (2.1.11)<br />

Defines which frequency reference place is selected for the PID controller.<br />

Applic.<br />

5 7<br />

Sel.<br />

0 AI1; terminals 2-3 AI1; terminals 2-3<br />

1 AI2; terminals 4-5 AI2; terminals 4-5<br />

2 PID ref. from menu M3, par. R34 AI3<br />

3<br />

Fieldbus ref.<br />

(FBProcess<strong>Data</strong>IN1)<br />

AI4<br />

4 Motor potentiometer reference PID ref. from menu M3, par. R34<br />

5 Fieldbus ref. (FBProcess<strong>Data</strong>IN1)<br />

6 Motor potentiometer reference<br />

Table 8-11. Selections for parameter ID332<br />

333 PID controller actual value selection 57 (2.2.8, 2.2.1.8)<br />

This parameter selects the PID controller actual value.<br />

0 Actual value 1<br />

1 Actual value 1 + Actual value 2<br />

2 Actual value 1 – Actual value 2<br />

3 Actual value 1 * Actual value 2<br />

4 Greater one of Actual value 1 and Actual value 2<br />

5 Smaller one of Actual value 1 and Actual value 2<br />

6 Mean value of Actual value 1 and Actual value 2<br />

7 Square root of Actual value 1 + Square root of Actual value 2<br />

334 Actual value 1 selection 57 (2.2.9, 2.2.1.9)<br />

335 Actual value 2 selection 57 (2.2.10, 2.2.1.10)<br />

0 Not used<br />

1 AI1 (control board)<br />

2 AI2 (control board)<br />

3 AI3<br />

4 AI4<br />

5 Fieldbus (Actual value 1: FBProcess<strong>Data</strong>IN2; Actual value 2: FBProcess<strong>Data</strong>IN3)<br />

Application 5<br />

6 Motor torque<br />

7 Motor speed<br />

8 Motor current<br />

9 Motor power<br />

10 Encoder frequency (for Actual value 1 only)<br />

336 Actual value 1 minimum scale 57 (2.2.11, 2.2.1.11)<br />

Sets the minimum scaling point for Actual value 1. See Figure 8-22.<br />

337 Actual value 1 maximum scale 57 (2.2.12, 2.2.1.12)<br />

Sets the maximum scaling point for Actual value 1. See Figure 8-22.<br />

338 Actual value 2 minimum scale 57 (2.2.13, 2.2.1.13)<br />

Sets the minimum scaling point for Actual value 2. See Figure 8-22.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!