154 Description of Parameters Honeywell<br />

366 Easy changeover 5 (2.2.37)<br />

0 Keep reference<br />

1 Copy reference<br />

If Copy reference has been selected it is possible to switch from direct control to PID<br />

control and back without scaling the reference and actual value.<br />

For example: The process is driven with direct frequency reference (Control place I/O B,<br />

fieldbus or keypad) to some point and then the control place is switched to one where<br />

the PID controller is selected. The PID control starts to maintain that point. The PID<br />

controller error value is forced to zero when the control place is changed.<br />

It is also possible to change the control source back to direct frequency control. In this<br />

case, the output frequency is copied as the frequency reference. If the destination place<br />

is Keypad the run status (Run/Stop, Direction and Reference) will be copied.<br />

The changeover is smooth when the reference of the destination source comes from the<br />

Keypad or an internal motor potentiometer (par. ID332 [PID Ref.] = 2 or 4, ID343 [I/O B<br />

Ref] = 2 or 4, par. ID121 [Keypad Ref] = 2 or 4 and ID122 [Fieldbus Ref]= 2 or 4.<br />

367 Motor potentiometer memory reset (Frequency reference) 3567 (2.2.23,<br />

2.2.28, 2.2.1.3, 2.2.1.16)<br />

0 No reset<br />

1 Memory reset in stop and powerdown<br />

2 Memory reset in powerdown<br />

370 Motor potentiometer memory reset (PID reference) 57 (2.2.29, 2.2.1.17)<br />

0 No reset<br />

1 Memory reset in stop and powerdown<br />

2 Memory reset in powerdown<br />

371 PID reference 2 (Place A additional reference) 7 (2.2.1.4)<br />

If the PID reference 2 enable input function (ID330)= TRUE, this parameter defines<br />

which reference place is selected as PID controller reference.<br />

0 = AI1 reference (terminals 2 and 3, e.g. potentiometer)<br />

1 = AI2 reference (terminals 5 and 6, e.g. transducer)<br />

2 = AI3 reference<br />

3 = AI4 reference<br />

4 = PID reference 1 from keypad<br />

5 = Reference from Fieldbus (FBProcess<strong>Data</strong>IN3)<br />

6 = Motor potentiometer<br />

7 = PID reference 2 from keypad<br />

If value 6 is selected for this parameter, the functions Motor potentiometer DOWN and<br />

Motor potentiometer UP must be connected to digital inputs (parameters ID417 and<br />

ID418).<br />

372 Supervised analogue input 7 (2.3.2.13)<br />

0 = Analogue reference from AI1 (terminals 2 and 3, e.g. potentiometer)<br />

1 = Analogue reference from AI2 (terminals 4 and 5, e.g. transducer)<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!