190 Description of Parameters Honeywell<br />

1001 Number of auxiliary drives 7 (2.9.1)<br />

With this parameter the number of auxiliary drives in use will be defined. The functions<br />

controlling the auxiliary drives (parameters ID458 to ID462) can be programmed to relay<br />

outputs or digital output. By default, one auxiliary drive is in use and it is programmed to<br />

relay output RO1 at B.1.<br />

1002 Start frequency, auxiliary drive 1 7 (2.9.2)<br />

The frequency of the drive controlled by the frequency drive must exceed the limit<br />

defined with these parameters with 1 Hz before the auxiliary drive is started. The 1 Hz<br />

overdraft makes a hysteresis to avoid unnecessary starts and stops. See Figure 8-54.<br />

See also parameters ID101 and ID102, page 122.<br />

1003 Stop frequency, auxiliary drive 1 7 (2.9.3)<br />

The frequency of the drive controlled by the frequency drive must fall with 1Hz below the<br />

limit defined with these parameters before the auxiliary drive is stopped. The stop<br />

frequency limit also defines the frequency to which the frequency of the drive controlled<br />

by the frequency drive is dropped after starting the auxiliary drive. See Figure 8-54.<br />

1004 Start frequency, auxiliary drive 2 7 (2.9.4)<br />

1005 Stop frequency, auxiliary drive 2 7 (2.9.5)<br />

1006 Start frequency, auxiliary drive 3 7 (2.9.6)<br />

1007 Stop frequency, auxiliary drive 3 7 (2.9.7)<br />

1008 Start frequency, auxiliary drive 4 7 (2.9.8)<br />

1009 Stop frequency, auxiliary drive 4 7 (2.9.9)<br />

See ID’s 1002 and 1003.<br />

1010 Start delay of auxiliary drives 7 (2.9.10)<br />

The frequency of the drive controlled by the frequency drive must remain above the start<br />

frequency of the auxiliary drive for the time defined with this parameter before the<br />

auxiliary drive is started. The delay defined applies to all auxiliary drives. This prevents<br />

unnecessary starts caused by momentary start limit exceedings. See Figure 8-54.<br />

1011 Stop delay of auxiliary drives 7 (2.9.11)<br />

The frequency of the drive controlled by the frequency drive must remain below the stop<br />

limit of the auxiliary drive for the time defined with this parameter before the drive is<br />

stopped. The delay defined applies to all auxiliary drives. This prevents unnecessary<br />

stops caused by momentary falls below the stop limit. See Figure 8-54.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!