Honeywell Description of Parameters 201<br />

1083 Follower torque reference selection 6 (2.11.4)<br />

Select the torque reference for the follower drive.<br />

1084 Control options 6 (2.4.22)<br />

These parameter functions depend on the Advance application version. The parameter<br />

is available for NXP drives only.<br />

b0=Disables encoder fault<br />

b1=Update Ramp Generator when MotorControlMode changes from TC (4) to SC (3)<br />

b2=RampUp; use acceleration ramp<br />

b3=RampDown; use deceleration ramp<br />

b4=FollowActual; follow actual speed value within WindowPos/NegWidth<br />

b5=TC ForceRampStop; Under stop request the speed limit forces the motor to stop<br />

1085 Brake On/Off current limit 6 (2.3.4.16)<br />

If motor current falls below this value the brake is closed immediately.<br />

This parameter is available for NXP drives only.<br />

1087 Scaling of generating torque limit 6 (2.2.6.6)<br />

0 = Parameter<br />

1 = AI1<br />

2 = AI2<br />

3 = AI3<br />

4 = AI4<br />

5 = FB limit scaling<br />

This signal will adjust the maximum motor generating torque between 0 and max. limit<br />

set with parameter ID1288. This parameter is available for NXP drives only.<br />

1088 Scaling of generating power limit 6 (2.2.6.8)<br />

0 Parameter<br />

1 AI1<br />

2 AI2<br />

3 AI3<br />

4 AI4<br />

5 FB limit scaling<br />

This signal will adjust the maximum motor generating power between 0 and max. limit<br />

set with parameter ID1290. This parameter is available for NXP drives only.<br />

1089 Follower stop function 6 (2.11.2)<br />

Defines how the follower drive stops.<br />

0 Coasting, follower remains in control even if master has stopped at fault<br />

1 Ramping, follower remains in control even if master has stopped at fault<br />

2 As master; follower behaves as master<br />

1090 Reset encoder counter 6 (2.2.7.29)<br />

Resets the monitoring values Shaft Angle and Shaft Rotations to zero.<br />

The parameter is available for NXP drives only.<br />

1092 Master Follower mode 2 6 (2.2.7.31)<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!