146 Description of Parameters Honeywell<br />

339 Actual value 2 maximum scale 57 (2.2.14, 2.2.1.14)<br />

Sets the maximum scaling point for Actual value 2. See Figure 8-22.<br />

100<br />

Scaled<br />

input signal [%]<br />

Scaled<br />

input signal [%]<br />

100<br />

ID336 = 30%<br />

ID337 = 80%<br />

76,5<br />

(15,3 mA)<br />

ID338 = -30%<br />

ID339 = 140%<br />

0<br />

0<br />

0<br />

4<br />

30<br />

80<br />

Analogue<br />

100 input [%]<br />

3,0<br />

8,0 10,0 V<br />

6,0<br />

16,0 20,0 mA<br />

8,8 16,8 20,0 mA<br />

Figure 8-22. Examples of actual value signal scaling<br />

-30<br />

17,7<br />

(3,5 mA)<br />

0<br />

0<br />

0<br />

4<br />

Analogue<br />

100 140 input [%]<br />

10,0 V<br />

20,0 mA<br />

20,0 mA<br />

NX12k34<br />

340 PID error value inversion 57 (2.2.32, 2.2.1.5)<br />

This parameter allows you to invert the error value of the PID controller (and thus the<br />

operation of the PID controller).<br />

0 No inversion<br />

1 Inverted<br />

341 PID reference rise time 57 (2.2.33, 2.2.1.6)<br />

Defines the time during which the PID controller reference rises from 0% to 100%.<br />

342 PID reference fall time 57 (2.2.34, 2.2.1.7)<br />

Defines the time during which the PID controller reference falls from 100% to 0%.<br />

343 I/O B reference selection 57 (2.2.5, 2.2.1.1)<br />

Defines the selected frequency reference place when the drive is controlled from the I/O<br />

terminal and reference place B is active (DIN6=closed).<br />

0 AI1 reference (terminals 2 and 3, e.g. potentiometer)<br />

1 AI2 reference (terminals 5 and 6, e.g. transducer)<br />

2 AI3 reference<br />

3 AI4 reference<br />

4 Keypad reference (parameter R32)<br />

5 Reference from Fieldbus (FBSpeedReference)<br />

6 Motor potentiometer reference<br />

7 PID controller reference<br />

- select actual value (par. ID333 to ID339) and the PID control reference (par. ID332)<br />

If value 6 is selected for this parameter in Application 5, the values of parameters ID319<br />

and ID301 are automatically set to 13.<br />

In Application 7, the functions Motorpotentiometer DOWN and Motorpotentiometer UP<br />

must be connected to digital inputs (parameters ID417 and ID418), if value 6 is selected<br />

for this parameter.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!