23.01.2015 Views

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

184 Description of Parameters Honeywell<br />

715 Underload protection, zero frequency load 234567 (2.7.19)<br />

The torque limit can be set between 5.0—150.0 % x TnMotor.<br />

This parameter gives value for the minimum torque allowed with zero frequency. See<br />

Figure 8-51.<br />

If you change the value of parameter ID113 (Motor nominal current) this parameter is<br />

automatically restored to the default value. See chapter 9.6.<br />

716 Underload time 234567 (2.7.20)<br />

This time can be set between 2.0 and 600.0 s.<br />

This is the maximum time allowed for an underload state to exist. An internal up/down<br />

counter counts the accumulated underload time. If the underload counter value goes<br />

above this limit the protection will cause a trip according to parameter ID713). If the drive<br />

is stopped the underload counter is reset to zero. See Figure 8-52 and chapter 9.6.<br />

Underload time counter<br />

Par. ID716<br />

Trip area<br />

Trip/warning<br />

par. ID713<br />

Time<br />

Underload<br />

No underl.<br />

NX12k66<br />

Figure 8-52. Underload time counter function<br />

717 Automatic restart: Wait time 234567 (2.8.1)<br />

Defines the time before the frequency drive tries to automatically restart the motor after<br />

the fault has disappeared.<br />

718 Automatic restart: Trial time 234567 (2.8.2)<br />

The Automatic restart function restarts the frequency drive when the faults selected with<br />

parameters ID720 to ID725 have disappeared and the waiting time has elapsed.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com