Honeywell Multi-purpose Control Application 75<br />

6.6.4.3 Analogue input 2 (Control keypad: Menu M2 G2.2.3)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.2.3.1<br />

AI2 signal<br />

selection<br />

0 A.2 388<br />

P2.2.3.2 AI2 filter time 0,00 10,00 s 0,10 329 0=No filtering<br />

P2.2.3.3 AI2 signal range 0 3 1 325<br />

0=0…100%*<br />

1=20…100%*<br />

2= -10V…+10V*<br />

3= Custom range*<br />

P2.2.3.4<br />

AI2 custom minimum<br />

-160,00<br />

setting<br />

160,00 % 20,00 326<br />

P2.2.3.5<br />

AI2 custom<br />

maximum setting<br />

-160,00 160,00 % 100,00 327<br />

P2.2.3.6<br />

AI2 reference<br />

scaling, minimum<br />

value<br />

0,00 320,00 Hz 0,00 393<br />

Selects the frequency that<br />

corresponds to the min.<br />

reference signal<br />

P2.2.3.7<br />

AI2 reference<br />

scaling, maximum<br />

value<br />

0,00 320,00 Hz 0,00 394<br />

P2.2.3.8<br />

AI2 joystick<br />

hysteresis<br />

0,00 20,00 % 0,00 395<br />

P2.2.3.9 AI2 sleep limit 0,00 100,00 % 0,00 396<br />

P2.2.3.10 AI2 sleep delay 0,00 320,00 s 0,00 397<br />

P2.2.3.11 AI2 joystick offset -100,00 100,00 % 0,00 166<br />

Table 6-8. Analogue input 2 parameters, G2.2.3<br />

6.6.4.4 Analogue input 3 (Control keypad: Menu M2 G2.2.4)<br />

Selects the frequency that<br />

corresponds to the max.<br />

reference signal<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.2.4.1<br />

AI3 signal<br />

selection<br />

0 0.1 141<br />

P2.2.4.2 AI3 filter time 0,00 10,00 s 0,00 142 0=No filtering<br />

P2.2.4.3 AI3 signal range 0 3 0 143<br />

0=0…100%<br />

1=20…100%<br />

2= -10V…+10V<br />

3=Custom range<br />

P2.2.4.4<br />

AI3 custom minimum<br />

-160,00<br />

setting<br />

160,00 % 0,00 144<br />

P2.2.4.5<br />

AI3 custom<br />

maximum setting<br />

-160,00 160,00 % 100,00 145<br />

P2.2.4.6 AI3 signal inversion 0 1 0 151<br />

0=Not inverted<br />

1=Inverted<br />

Table 6-9. Analogue input 3 parameters, G2.2.4<br />

**Remember to place jumpers of block X2 accordingly.<br />

See the product's User's <strong>Manual</strong>.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!