Honeywell Description of Parameters 155<br />

373 Analogue input limit supervision 7 (2.3.2.14)<br />

If the value of the selected analogue input goes under/over the set limit (par. ID374) this<br />

function generates a warning message through the digital output or the relay outputs<br />

depending on to which output the supervision function (par. ID4<strong>63</strong>) is connected.<br />

0 No supervision<br />

1 Low limit supervision<br />

2 High limit supervision<br />

374 Analogue input supervised value 7 (2.3.2.15)<br />

The value of the selected analogue input to be supervised by parameter ID373.<br />

375 Analogue output offset 67 (2.3.5.7, 2.3.3.7)<br />

Add –100.0 to 100.0% to the analogue output.<br />

376 PID sum point reference (Place A direct reference) 5 (2.2.4)<br />

Defines which reference source is added to PID controller output if PID controller is<br />

used.<br />

0 No additional reference (Direct PID output value)<br />

1 PID output + AI1 reference from terminals 2 and 3 (e.g. potentiometer)<br />

2 PID output + AI2 reference from terminals 4 and 5 (e.g. transducer)<br />

3 PID output + PID keypad reference<br />

4 PID output + Fieldbus reference (FBSpeedReference)<br />

5 PID output + Motor potentiometer reference<br />

6 Fieldbus + PID output (Process<strong>Data</strong>IN3)<br />

7 Motor potentiometer + PID output<br />

If value 7 is selected for this parameter, the values of parameters ID319 and ID301 are<br />

automatically set to 13. See Figure 8-33.<br />

Hz<br />

30,00<br />

20,00<br />

PID Max limit<br />

PID Min limit<br />

Figure 8-33. PID sum point reference<br />

t<br />

Note: The maximum and minimum limits illustrated in the picture limit only the PID<br />

output, no other outputs.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!