148 Description of Parameters Honeywell<br />

349 Torque limit, supervision value 34567 (2.3.15, 2.3.4.6, 2.3.2.6)<br />

Set here the torque value to be supervised by parameter ID348.<br />

Applications 3 and 4:<br />

Torque supervision value can be reduced below the setpoint with external free analogue<br />

input signal, see parameters ID361 and ID362.<br />

350 Reference limit, supervision function 34567 (2.3.16, 2.3.4.7, 2.3.2.7)<br />

0 = No supervision<br />

1 = Low limit supervision<br />

2 = High limit supervision<br />

If the reference value falls below or exceeds the set limit (ID351), this function generates<br />

a warning message via the digital output DO1 or via a relay output RO1 or RO2<br />

1) depending on the settings of parameters ID312 to ID314 (applications 3,4,5) or<br />

2) depending on to which output the supervision signal (par. ID449) is connected<br />

(applications 6 and 7).<br />

The supervised reference is the current active reference. It can be place A or B<br />

reference depending on DIN6 input, or panel reference if the panel is the active control<br />

place.<br />

351 Reference limit, supervision value 34567 (2.3.17, 2.3.4.8, 2.3.2.8)<br />

The frequency value to be supervised with the parameter ID350.<br />

352 External brake-off delay 34567 (2.3.18, 2.3.4.9, 2.3.2.9)<br />

353 External brake-on delay 34567 (2.3.19, 2.3.4.10, 2.3.2.10)<br />

The function of the external brake can be timed to the start and stop control signals with<br />

these parameters. See Figure 8-24 and chapter 9.1 on page 210.<br />

The brake control signal can be programmed via the digital output DO1 or via one of the<br />

relay outputs RO1 and RO2, see parameters ID312 to ID314 (applications 3,4,5) or<br />

ID445 (applications 6 and 7).<br />

a)<br />

b)<br />

t OFF<br />

= ID352 t ON<br />

= ID353 t OFF<br />

= ID352 t ON<br />

= Par. ID353<br />

External<br />

BRAKE: OFF<br />

ON<br />

DO1/RO1/<br />

RO2<br />

External<br />

BRAKE: OFF<br />

ON<br />

DO1/RO1/<br />

RO2<br />

DIN1: RUN FWD<br />

STOP<br />

DIN1: START<br />

PULSE<br />

DIN2: RUN REV<br />

STOP<br />

NX12K45<br />

t<br />

DIN2: STOP<br />

PULSE<br />

t<br />

Figure 8-24. External brake control:<br />

a) Start/Stop logic selection, ID300 = 0, 1 or 2<br />

b) Start/Stop logic selection, ID300= 3<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!