Honeywell Pump and Fan Control Application 97<br />

7.2 Control I/O<br />

Reference potentiometer,<br />

1…10 kΩ<br />

2-wire<br />

transmitter<br />

Actual<br />

value I<br />

(0)4…20 mA<br />

FAULT<br />

–<br />

+<br />

OPT-A1<br />

Terminal Signal Description<br />

1 +10V ref Reference output Voltage for potentiometer, etc.<br />

2 AI1+ Analogue input, voltage range<br />

0—10V DC<br />

Voltage input frequency reference<br />

3 AI1- I/O Ground Ground for reference and controls<br />

4 AI2+ Analogue input, current range Current input frequency reference<br />

5 AI2- 0—20mA<br />

6 +24V Control voltage output Voltage for switches, etc. max 0.1 A<br />

7 GND I/O ground Ground for reference and controls<br />

8 DIN1 Start/Stop; Control place A Contact closed = start<br />

(PID controller) (programm.)<br />

9 DIN2 Interlock 1<br />

(programmable)<br />

Contact closed = Interlock used<br />

Contact open = Interlock not used<br />

10 DIN3 Interlock 2<br />

(programmable)<br />

Contact closed = Interlock used<br />

Contact open = Interlock not used<br />

11 CMA Common for DIN 1—DIN 3 Connect to GND or +24V<br />

12 +24V Control voltage output Voltage for switches (see #6)<br />

13 GND I/O ground Ground for reference and controls<br />

14 DIN4 Start/Stop Control place B Contact closed = Start<br />

(Direct frequency reference)<br />

(programmable)<br />

15 DIN5 Jogging speed selection Contact closed = Jogging speed active<br />

(programmable)<br />

16 DIN6 Control place A/B selection<br />

(programmable)<br />

Contact open = Control place A is active<br />

Contact closed = Control place B is active<br />

17 CMB Common for DIN4—DIN6 Connect to GND or +24V<br />

18 AO1+ Output frequency<br />

Programmable; See chapters 7.5.4.3,<br />

19 AO1-<br />

(GND)<br />

Analogue output<br />

7.5.4.4 and 7.5.4.5<br />

Range 0—20 mA/R L , max. 500Ω<br />

20 DO1 Digital output<br />

FAULT<br />

OPT-A2<br />

21 RO1<br />

22 RO1<br />

23 RO1<br />

Relay output 1<br />

Aux/Autochange 1<br />

Programmable<br />

Open collector, I≤50mA, U≤48 VDC<br />

Programmable; See chapter 7.5.4.1<br />

220<br />

VAC<br />

24 RO2<br />

25 RO2<br />

26 RO2<br />

Relay output 2<br />

Aux/Autochange 2<br />

Programmable; See chapter 7.5.4.1<br />

Table 7-1. Pump and fan control application default I/O configuration and<br />

connection example (with 2-wire transmitter).<br />

Note: See jumper selections below. More<br />

information in the product's user's<br />

manual.<br />

Jumper block X3:<br />

CMA and CMB grounding<br />

CMB connected to GND<br />

CMA connected to GND<br />

CMB isolated from GND<br />

CMA isolated from GND<br />

CMB and CMA<br />

internally connected together,<br />

isolated from GND<br />

= Factory default<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!