Honeywell Multi-purpose Control Application 77<br />
6.6.4.7 Digital inputs (Control keypad: Menu M2 G2.2.4)<br />
Code Parameter Min Default Cust ID Note<br />
P2.2.7.1 Start signal 1 0 A.1 403<br />
P2.2.7.2 Start signal 2 0 A.2 404<br />
P2.2.7.3 Run enable 0 0.2 407 Motor start enabled (cc)<br />
P2.2.7.4 Reverse 0 0.1 412<br />
P2.2.7.5 Preset speed 1 0 0.1 419<br />
P2.2.7.6 Preset speed 2 0 0.1 420<br />
P2.2.7.7 Preset speed 3 0 0.1 421<br />
P2.2.7.8<br />
Motor potentiometer<br />
reference DOWN<br />
0 0.1 417<br />
P2.2.7.9<br />
Motor potentiometer<br />
reference UP<br />
0 0.1 418<br />
Direction forward (oc)<br />
Direction reverse (cc)<br />
See preset speeds in Basic<br />
Parameters (G2.1)<br />
Mot.pot. reference decreases<br />
(cc)<br />
Mot.pot. reference increases<br />
(cc)<br />
P2.2.7.10 Fault reset 0 0.1 414 All faults reset (cc)<br />
P2.2.7.11 External fault (close) 0 0.1 405 Ext. fault displayed (cc)<br />
P2.2.7.12 External fault (open) 0 0.2 406 Ext. fault displayed (oc)<br />
P2.2.7.13 Acc/Dec time selection 0 0.1 408<br />
Acc/Dec time 1 (oc)<br />
Acc/Dec time 2 (cc)<br />
P2.2.7.14 Acc/Dec prohibit 0 0.1 415 Acc/Dec prohibited (cc)<br />
P2.2.7.15 DC braking 0 0.1 416 DC braking active (cc)<br />
P2.2.7.16 Jogging speed 0 A.4 413<br />
Jogging speed selected for<br />
frequency reference (cc)<br />
P2.2.7.17 AI1/AI2 selection 0 0.1 422<br />
P2.2.7.18 Control from I/O terminal 0 0.1 409<br />
Force control place to I/O<br />
terminal (cc)<br />
P2.2.7.19 Control from keypad 0 0.1 410<br />
Force control place to<br />
keypad (cc)<br />
P2.2.7.20 Control from fieldbus 0 0.1 411<br />
Force control place to<br />
fieldbus (cc)<br />
P2.2.7.21<br />
Parameter set 1/set 2<br />
Closed cont.=Set 2 is used<br />
0 0.1 496<br />
selection<br />
Open cont.=Set 1 is used<br />
P2.2.7.22 Motor control mode 1/2 0 0.1 164<br />
Closed cont.=Mode 2 is used<br />
Open cont.=Mode 1 is used<br />
See par 2.6.1, 2.6.12<br />
NXP drives only<br />
P2.2.7.23 Cooling monitor 0 0.2 750 Used with liquid-cooled unit<br />
P2.2.7.24<br />
External brake<br />
Monitoring signal from<br />
0 0.2 1210<br />
acknowledge<br />
mechanical brake<br />
P2.2.7.25 Prevention of startup 0 0.2 1420 Safety switch input<br />
P2.2.7.26 Enable inching 0 0.1 532 Enables Inching function<br />
P2.2.7.27 Inching reference 1 0 0.1 530<br />
Inching reference 1. This will<br />
start the drive<br />
P2.2.7.28 Inching reference 2 0 0.1 531<br />
Inching reference 2. This will<br />
start the drive<br />
P2.2.7.29 Reset encoder counter 0 0.1 1090<br />
Reset monitoring signals,<br />
shaft rounds and angle<br />
P2.2.7.30 Emergency stop 0 0.2 1213<br />
P2.2.7.31 Master Follower mode 2 0 0.1 1092<br />
P2.2.7.32<br />
Input switch<br />
acknowledgement<br />
0 0.2 1209<br />
Table 6-12. Digital input signals, G2.2.4<br />
cc = closing contact<br />
oc = opening contact<br />
Automation and Control Solutions<br />