5<br />

34(110) Installation<br />

5.2 Cooling<br />

Enough free space should be left around the frequency drive to ensure sufficient air circulation<br />

and cooling. The required dimensions for free space are in the table below.<br />

If several units are mounted above each other the the required free space between the stacked<br />

units equals C + D (see figure below). Moreover, the outlet air used for cooling by the lower unit<br />

must be directed away from the inlet air to be used by the upper unit.<br />

5.2.1 FR4 to FR9<br />

Type<br />

Dimensions (inch)<br />

A A 2 B C D<br />

<strong>NXS</strong> 0010—0040 B 0.79 0.79 3.94 1.97<br />

<strong>NXS</strong> 0015—0075 A<br />

<strong>NXS</strong> 0050—0100 B 0.79 0.79 4.72 2.36<br />

<strong>NXS</strong> 0100—0200 A<br />

<strong>NXS</strong> 0150—0200 B 1.18 0.79 6.3 3.15<br />

<strong>NXS</strong> 0250—0400 A<br />

<strong>NXS</strong> 0250—0400 B 3.15 3.15 11.8 3.94<br />

<strong>NXS</strong> 0500—0750 A<br />

<strong>NXS</strong> 1000—1500 A 0.79 7.87 3.15 11.8 7.87<br />

(5.91*)<br />

Table 5-9. Mounting space dimensions<br />

A = clearance around the freq. converter (see also A 2 and B)<br />

A 2 = clearance needed on either side of the frequency converter<br />

for fan change (without disconneting the motor cables)<br />

* = min. clearance for fan change (without disconnecting the<br />

motor cables) between two frequency converters<br />

B = distance from one frequency converter to another or<br />

distance to cabinet wall<br />

C = free space above the frequency converter<br />

D = free space underneath the frequency converter<br />

Type<br />

<strong>NXS</strong> 0010—0040 B<br />

<strong>NXS</strong> 0015—0075 A<br />

<strong>NXS</strong> 0050—0100 B<br />

<strong>NXS</strong> 0100—0200 A<br />

<strong>NXS</strong> 0150—0200 B<br />

<strong>NXS</strong> 0250—0400 A<br />

<strong>NXS</strong> 0250—0400 B<br />

<strong>NXS</strong> 0500—0750 A<br />

<strong>NXS</strong> 0041—0062 C<br />

<strong>NXS</strong> 0500—0750 B<br />

<strong>NXS</strong> 1000—1500 A<br />

<strong>NXS</strong> 1750—2000 A<br />

<strong>NXS</strong> 0144—0208 C<br />

Table 5-10. Required cooling air.<br />

C<br />

B<br />

A<br />

A<br />

A 2 A 2<br />

D<br />

Figure 5-10. Installation space<br />

Cooling air required [CFM)<br />

42<br />

112<br />

251<br />

251<br />

383<br />

766<br />

NK5_2<br />

B<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com