Honeywell Description of Parameters 183<br />

711 Stall time 234567 (2.7.15)<br />

This time can be set between 1.0 and<br />

120.0s.<br />

This is the maximum time allowed for a<br />

stall stage. The stall time is counted by an<br />

internal up/down counter.<br />

If the stall time counter value goes above<br />

this limit the protection will cause a trip<br />

(see ID709). See chapter 9.5.<br />

Par. ID711<br />

Stall time counter<br />

Trip area<br />

Trip/warning<br />

par. ID709<br />

Time<br />

Stall<br />

No stall<br />

NX12k64<br />

712 Stall frequency limit 234567 (2.7.16)<br />

Par. ID714<br />

Figure 8-50. Stall time count<br />

The frequency can be set between 1-f max (ID102).<br />

For a stall state to occur, the output frequency must have remained below this limit. See<br />

chapter 9.5.<br />

713 Underload protection 234567 (2.7.17)<br />

0 = No response<br />

1 = Warning<br />

2 = Fault, stop mode after fault according to ID506<br />

3 = Fault, stop mode after fault always by coasting<br />

If tripping is set active the drive will stop and activate the fault stage.<br />

Deactivating the protection by setting the parameter to 0 will reset the underload time<br />

counter to zero. See chapter 9.6.<br />

714 Underload protection, field weakening area load 234567 (2.7.18)<br />

The torque limit can be set between<br />

10.0—150.0 % x T nMotor .<br />

This parameter gives the value for<br />

the minimum torque allowed when<br />

the output frequency is above the<br />

field weakening point. See Figure<br />

8-51.<br />

Torque<br />

If you change parameter ID113<br />

(Motor nominal current) this parameter<br />

is automatically restored to<br />

the default value. See chapter 9.6.<br />

Par. ID715<br />

Underload area<br />

f<br />

5 Hz<br />

Fieldweakening<br />

point par. ID602<br />

NX12k65<br />

Figure 8-51. Setting of minimum load<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!