186 Description of Parameters Honeywell<br />

721 Automatic restart: Number of tries after overvoltage trip 234567 (2.8.5)<br />

This parameter determines how many automatic restarts can be made during the trial<br />

time set by parameter ID718 after an overvoltage trip.<br />

0 = No automatic restart after overvoltage fault trip<br />

>0 = Number of automatic restarts after overvoltage fault trip. The fault is<br />

reset and the drive is started automatically after the DC-link voltage<br />

has returned to the normal level.<br />

722 Automatic restart: Number of tries after overcurrent trip 234567 (2.8.6)<br />

(NOTE! IGBT temp fault also included)<br />

This parameter determines how many automatics restarts can be made during the trial<br />

time set by ID718.<br />

0 = No automatic restart after overcurrent fault trip<br />

>0 = Number of automatic restarts after overcurrent trip and IGBT<br />

temperature faults.<br />

723 Automatic restart: Number of tries after 4mA reference trip 234567 (2.8.7)<br />

This parameter determines how many automatics restarts can be made during the trial<br />

time set by ID718.<br />

0 = No automatic restart after reference fault trip<br />

>0 = Number of automatic restarts after the analogue current signal<br />

(4…20mA) has returned to the normal level (>4mA)<br />

725 Automatic restart: Number of tries after external fault trip 234567 (2.8.9)<br />

This parameter determines how many automatics restarts can be made during the trial<br />

time set by ID718.<br />

0 = No automatic restart after External fault trip<br />

>0 = Number of automatic restarts after External fault trip<br />

726 Automatic restart: Number of tries<br />

after motor temperature fault trip 234567 (2.8.8)<br />

This parameter determines how many automatics restarts can be made during the trial<br />

time set by ID718.<br />

0 = No automatic restart after Motor temperature fault trip<br />

>0 = Number of automatic restarts after the motor temperature has<br />

returned to its normal level<br />

727 Response to undervoltage fault 234567 (2.7.5)<br />

0 = Fault stored in fault history<br />

1 = Fault not stored in fault history<br />

For the undervoltage limits, see the product's user's manual.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!