138 Description of Parameters Honeywell<br />

307 Analogue output function (2.16, 2.3.2, 2.3.5.2, 2.3.3.2)<br />

This parameter selects the desired function for the analogue output signal.<br />

See pages 9, 17, 29, 42, 56, 81 and 114 for the parameter values available in the<br />

respective application.<br />

308 Analogue output filter time 234567 (2.3.3, 2.3.5.3, 2.3.3.3)<br />

Defines the filtering time of the analogue<br />

output signal.<br />

Setting this parameter value 0 will<br />

deactivate filtering.<br />

%<br />

100%<br />

Unfiltered signal<br />

<strong>63</strong>%<br />

Filtered signal<br />

t [s]<br />

ID308<br />

Figure 8-13. Analogue output filtering<br />

NX12K16<br />

309 Analogue output inversion 234567 (2.3.4, 2.3.5.4, 2.3.3.4)<br />

Inverts the analogue output signal:<br />

Maximum output signal = Minimum set value<br />

Minimum output signal = Maximum set value<br />

Analog<br />

output<br />

current<br />

20 mA<br />

See parameter ID311 below.<br />

12 mA<br />

10 mA<br />

4 mA<br />

0 mA<br />

0<br />

0.5<br />

ID311 =<br />

200%<br />

Max. value of signal<br />

selected with ID307<br />

1.0<br />

ID311=<br />

50%<br />

ID311 =<br />

100%<br />

NX12K17<br />

Figure 8-14. Analogue output invert<br />

310 Analogue output minimum 234567 (2.3.5, 2.3.5.5, 2.3.3.5)<br />

Defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in<br />

analogue output scaling in parameter ID311 (Figure 8-15).<br />

0 Set minimum value to 0 mA<br />

1 Set minimum value to 4 mA<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!