Cabling and connections <strong>63</strong>(110)<br />

6.2.2.1 Control cables<br />

The control cables shall be at least 0.0008 in 2 screened multicore cables, see Table 6-1. The<br />

maximum terminal wire size is 0.004 in 2 for the relay terminals and 0.002 in 2 for other terminals.<br />

Find the tightening torques of the option board terminals in Table below.<br />

Terminal Tightening torque<br />

screw Nm lb-in.<br />

Relay and<br />

thermistor<br />

terminals<br />

0.5 4.5<br />

(screw M3)<br />

Other terminals<br />

(screw M2.6)<br />

0.2 1.8<br />

Table 6-8. Tightening torques of terminals<br />

6.2.2.2 Galvanic isolation barriers<br />

The control connections are isolated from the mains potential and the GND terminals are<br />

permanently connected to ground. See Figure 6-17.<br />

The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally<br />

double-isolated from each other at 300VAC (EN-50178).<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com<br />

6