144 Description of Parameters Honeywell<br />

325 Analogue input AI2 signal range 34567 (2.2.10, 2.2.22, 2.2.3.3)<br />

Applic. 3, 4 5 6 7<br />

Sel.<br />

0 0…20mA 0…20mA 0…100% 0…100%<br />

1 4…20mA 4mA/20…100% 20…100% 20…100%<br />

2 Customised Customised –10…+10V Customised<br />

3 Customised<br />

Table 8-10. Selections for parameter ID325<br />

Output<br />

frequency<br />

ID304<br />

ID325 = Custom<br />

ID325 = 0<br />

AI2 = 0—100%<br />

ID303<br />

ID325 = 1<br />

AI2 = 20-100%<br />

AI2<br />

(term. 3,4)<br />

Figure 8-21. Analogue input AI2 scaling.<br />

326 Analogue input AI2 custom setting min. 34567 (2.2.11, 2.2.23, 2.2.3.4)<br />

327 Analogue input AI2 custom setting max. 34567 (2.2.12, 2.2.24, 2.2.3.5)<br />

These parameters set AI2 for any input signal span within -160…160%.<br />

328 Analogue input AI2 inversion 3457 (2.2.13, 2.2.25, 2.2.3.6)<br />

See ID323.<br />

Note: In application 3, AI2 is the place A frequency reference, if parameter ID117 = 1<br />

(default)<br />

329 Analogue input AI2 (I in ) filter time 34567 (2.2.14, 2.2.26, 2.2.3.2)<br />

See ID324.<br />

330 DIN5 function 5 (2.2.3)<br />

The digital input DIN5 has 14 possible functions. If it need not be used, set the value of<br />

this parameter to 0.<br />

The selections are the same as in parameter ID319 except:<br />

13 Enable PID reference 2<br />

Contact open: PID controller reference selected with parameter ID332.<br />

Contact closed: PID controller keypad reference 2 selected with parameter R3.5.<br />

331 Motor potentiometer ramp time 3567 (2.2.22, 2.2.27, 2.2.1.2, 2.2.1.15)<br />

Defines the speed of change of the motor potentiometer value (Hz/s).<br />

0<br />

ID326<br />

4 mA<br />

ID327<br />

20 mA<br />

NX12K75<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!