160 Description of Parameters Honeywell<br />

402 Reducing of torque supervision limit 6 (2.2.6.4)<br />

See ID399.<br />

The set torque supervision limit can<br />

be reduced with the free analogue<br />

input signal between 0 and the set<br />

supervision limit, ID349. See Figure<br />

8-39.<br />

100%<br />

Par. ID349<br />

Torque<br />

limit<br />

403 Start signal 1 6 (2.2.7.1)<br />

Signal selection 1 for the start/stop logic.<br />

Default programming A.1.<br />

404 Start signal 2 6 (2.2.7.2)<br />

Signal selection 2 for the start/stop logic.<br />

Default programming A.2.<br />

405 External fault (close) 67 (2.2.7.11, 2.2.6.4)<br />

Contact closed:<br />

Fault is displayed and motor stopped.<br />

406 External fault (open) 67 (2.2.7.12, 2.2.6.5)<br />

Contact open:<br />

Fault is displayed and motor stopped.<br />

407 Run enable 67 (2.2.7.3, 2.2.6.6)<br />

Contact open:<br />

Contact closed:<br />

Start of motor disabled<br />

Start of motor enabled<br />

Signal<br />

range<br />

Free<br />

analogue<br />

input<br />

0 NX12K60<br />

Figure 8-39. Reducing torque supervision limit<br />

408 Acceleration/Deceleration time selection 67 (2.2.7.13, 2.2.6.7)<br />

Contact open:<br />

Contact closed:<br />

Acceleration/Deceleration time 1 selected<br />

Acceleration/Deceleration time 2 selected<br />

Set Acceleration/Deceleration times with parameters ID103 and ID104.<br />

409 Control from I/O terminal 67 (2.2.7.18, 2.2.6.8)<br />

Contact closed:<br />

Force control place to I/O terminal<br />

410 Control from keypad 67 (2.2.7.19, 2.2.6.9)<br />

Contact closed:<br />

Force control place to keypad<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />