Honeywell Description of Parameters 153<br />

3 3-wire connection (pulse control):<br />

DIN4: closed contact = start pulse<br />

DIN5: open contact = stop pulse<br />

(DIN3 can be programmed for reverse command)<br />

See Figure 8-32.<br />

Output<br />

frequency<br />

Stop function<br />

(ID506)<br />

= coasting<br />

If Start and Stop pulses are<br />

simultaneous the Stop pulse<br />

overrides the Start pulse<br />

t<br />

REV<br />

DIN4<br />

Start<br />

DIN5<br />

Stop<br />

Figure 8-32. Start pulse/ Stop pulse.<br />

NX012K11<br />

The selections 4 to 6 shall be used to exclude the possibility of an unintentional start<br />

when, for example, power is connected, re-connected after a power failure, after a fault<br />

reset, after the drive is stopped by Run Enable (Run Enable = False) or when the control<br />

place is changed. The Start/Stop contact must be opened before the motor can be<br />

started.<br />

4 DIN4: closed contact = start forward (Rising edge required to start)<br />

DIN5: closed contact = start reverse (Rising edge required to start)<br />

5 DIN4: closed contact = start (Rising edge required to start)<br />

open contact = stop<br />

DIN5: closed contact = reverse<br />

open contact = forward<br />

6 DIN4: closed contact = start (Rising edge required to start)<br />

open contact = stop<br />

DIN5: closed contact = start enabled<br />

open contact = start disabled and drive stopped if running<br />

364 Reference scaling, minimum value, place B 3 (2.2.18)<br />

365 Reference scaling, maximum value, place B 3 (2.2.19)<br />

See parameters ID303 and ID304 above.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!