120 Pump and Fan Control Application Honeywell<br />

7.5.10 Pump and fan control parameters (Control keypad: Menu M2 G2.9)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.9.1<br />

Number of auxiliary<br />

drives<br />

0 4 1 1001<br />

P2.9.2<br />

Start frequency, Par.<br />

auxiliary drive 1 2.9.3<br />

320,00 Hz 51,00 1002<br />

P2.9.3<br />

Stop frequency, Par. Par.<br />

auxiliary drive 1 2.1.1 2.9.2<br />

Hz 10,00 1003<br />

P2.9.4<br />

Start frequency, Par.<br />

auxiliary drive 2 2.9.5<br />

320,00 Hz 51,00 1004<br />

P2.9.5<br />

Stop frequency, Par. Par.<br />

auxiliary drive 2 2.1.1 2.9.4<br />

Hz 10,00 1005<br />

P2.9.6<br />

Start frequency, Par.<br />

auxiliary drive 3 2.9.7<br />

320,00 Hz 51,00 1006<br />

P2.9.7<br />

Stop frequency, Par. Par.<br />

auxiliary drive 3 2.1.1 2.9.6<br />

Hz 10,00 1007<br />

P2.9.8<br />

Start frequency, Par.<br />

auxiliary drive 4 2.9.9<br />

320,00 Hz 51,00 1008<br />

P2.9.9<br />

Stop frequency, Par. Par.<br />

auxiliary drive 4 2.1.1 2.9.8<br />

Hz 10,00 1009<br />

P2.9.10<br />

Start delay,<br />

auxiliary drives<br />

0,0 300,0 s 4,0 1010<br />

P2.9.11<br />

Stop delay,<br />

auxiliary drives<br />

0,0 300,0 s 2,0 1011<br />

P2.9.12<br />

Reference step,<br />

auxiliary drive 1<br />

0,0 100,0 % 0,0 1012<br />

P2.9.13<br />

Reference step,<br />

auxiliary drive 2<br />

0,0 100,0 % 0,0 1013<br />

P2.9.14<br />

Reference step,<br />

auxiliary drive 3<br />

0,0 100,0 % 0,0 1014<br />

P2.9.15<br />

Reference step,<br />

auxiliary drive 4<br />

0,0 100,0 % 0,0 1015<br />

P2.9.16<br />

PID controller<br />

bypass<br />

0 1 0 1020 1=PID contr. bypassed<br />

P2.9.17<br />

Analogue input<br />

selection for input<br />

pressure<br />

measurement<br />

0 5 0 1021<br />

P2.9.18<br />

Input pressure<br />

high limit<br />

0,0 100,0 % 30,00 1022<br />

P2.9.19<br />

Input pressure<br />

low limit<br />

0,0 100,0 % 20,00 1023<br />

P2.9.20 Output pressure drop 0,0 100,0 % 30,00 1024<br />

P2.9.21<br />

P2.9.22<br />

Frequency drop<br />

delay<br />

Frequency increase<br />

delay<br />

0,0 300,0 s 0,0 1025<br />

0,0 300,0 s 0,0 1026<br />

P2.9.23 Interlock selection 0 2 1 1032<br />

P2.9.24 Autochange 0 1 1 1027<br />

P2.9.25<br />

Autoch. and interl.<br />

automatics selection<br />

0 1 1 1028<br />

0=Not used<br />

1=AI1<br />

2=AI2<br />

3=AI3<br />

4=AI4<br />

5=Fieldbus signal<br />

(FBProcess<strong>Data</strong>IN3)<br />

0=No delay<br />

300=No frequency drop<br />

nor increase<br />

0=No delay<br />

300=No frequency drop<br />

nor increase<br />

0=Interlocks not used<br />

1=Set new interlock last;<br />

update order after<br />

value of par. 2.9.26 or<br />

Stop state<br />

2=Stop and update order<br />

immediately<br />

0=Not used<br />

1=Autochange used<br />

0=Auxiliary drives only<br />

1=All drives<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!