Honeywell Description of Parameters 141<br />

316 Output frequency limit supervision value 234567 (2.3.11, 2.3.4.2, 2.3.2.2)<br />

Selects the frequency value supervised by parameter ID315. See Figure 8-16.<br />

f[Hz]<br />

ID315 = 2<br />

ID316<br />

t<br />

Example:<br />

21 RO1<br />

22 RO1<br />

23 RO1<br />

21 RO1<br />

22 RO1<br />

23 RO1<br />

21 RO1<br />

22 RO1<br />

23 RO1<br />

Figure 8-16. Output frequency supervision<br />

NX12K19<br />

319 DIN2 function 5 (2.2.1)<br />

This parameter has 14 selections. If digital input DIN2 need not be used, set the<br />

parameter value to 0.<br />

1 External fault<br />

Contact closed: Fault is displayed and motor stopped when the input is active<br />

2 External fault<br />

Contact open: Fault is displayed and motor stopped when the input is not active<br />

3 Run enable<br />

Contact open: Start of motor disabled<br />

Contact closed: Start of motor enabled<br />

4 Acceleration or deceleration time selection<br />

Contact open: Acceleration/Deceleration time 1 selected<br />

Contact closed: Acceleration/Deceleration time 2 selected<br />

5 Closing contact: Force control place to I/O terminal<br />

6 Closing contact: Force control place to keypad<br />

7 Closing contact: Force control place to fieldbus<br />

When the control place is forced to change the values of Start/Stop, Direction and<br />

Reference valid in the respective control place are used (reference according to<br />

parameters ID343, ID121 and ID122).<br />

Note: The value of ID125 (Keypad Control Place) does not change.<br />

When DIN2 opens the control place is selected according to keypad control place<br />

selection.<br />

8 Reverse<br />

Contact open: Forward<br />

Contact closed: Reverse<br />

If several inputs are programmed to reverse, one<br />

active contact is enough to set the direction to<br />

9 Jogging speed (see par. ID124) reverse.<br />

Contact closed: Jogging speed selected for frequency reference<br />

10 Fault reset<br />

Contact closed: All faults reset<br />

11 Acceleration/Deceleration prohibited<br />

Contact closed: No acceleration or deceleration possible until the contact is opened<br />

Automation and Control Solutions<br />

Honeywell<br />