Honeywell Description of Parameters 161<br />

411 Control from fieldbus 67 (2.2.7.20, 2.2.6.10)<br />

Contact closed:<br />

Force control place to fieldbus<br />

NOTE: When the control place is forced to change the values of Start/Stop, Direction<br />

and Reference valid in the respective control place are used.<br />

The value of parameter ID125 (Keypad Control Place) does not change.<br />

When the input opens the control place is selected according to keypad control<br />

parameter ID125.<br />

412 Reverse 67 (2.2.7.4, 2.2.6.11)<br />

Contact open:<br />

Contact closed:<br />

Direction forward<br />

Direction reverse<br />

413 Jogging speed 67 (2.2.7.16, 2.2.6.12)<br />

Contact closed: Jogging speed selected for frequency reference<br />

See parameter ID124.<br />

Default programming: A.4.<br />

414 Fault reset 67 (2.2.7.10, 2.2.6.13)<br />

Contact closed:<br />

All faults are reset.<br />

415 Acceleration/Deceleration prohibited 67 (2.2.7.14, 2.2.6.14)<br />

Contact closed:<br />

No acceleration or deceleration possible until the contact is opened.<br />

416 DC-braking 67 (2.2.7.15, 2.2.6.15)<br />

Contact closed:<br />

In STOP mode, the DC braking operates until the contact is opened.<br />

417 Motor potentiometer DOWN 67 (2.2.7.8, 2.2.6.16)<br />

Contact closed:<br />

opened.<br />

Motor potentiometer reference DECREASES until the contact is<br />

418 Motor potentiometer UP 67 (2.2.7.9, 2.2.6.17)<br />

Contact closed:<br />

opened.<br />

Motor potentiometer reference INCREASES until the contact is<br />

419 Preset speed 1 6 (2.2.7.5)<br />

420 Preset speed 2 6 (2.2.7.6)<br />

421 Preset speed 3 6 (2.2.7.7)<br />

Parameter values are automatically limited between the minimum and maximum<br />

frequencies (parameters ID101 and ID102).<br />

422 AI1/AI2 selection 6 (2.2.7.17)<br />

With this parameter you can select either AI1 or AI2 signal for frequency reference.<br />

423 Start A signal 7 (2.2.6.1)<br />

Start command from control place A.<br />

Default programming: A.1<br />

Automation and Control Solutions<br />

Honeywell<br />